🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 150 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.91%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.34V (1.13%)
Voltage at Load End206.1 VLoss: 1.9 V (1395.2 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 150 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A346.26 V (166.47%)0.0 V571.17 V (274.6%)254891.7 WDrop/Amp High
12 AWG3.31 mm²20 A217.59 V (104.61%)0.0 V358.92 V (172.56%)160173.7 WDrop/Amp High
10 AWG5.26 mm²30 A136.93 V (65.83%)71.1 V225.86 V (108.59%)100793.7 WDrop/Amp High
8 AWG8.37 mm²50 A86.05 V (41.37%)122.0 V141.94 V (68.24%)63342.3 WDrop/Amp High
6 AWG13.3 mm²65 A54.15 V (26.03%)153.8 V89.33 V (42.95%)39862.8 WDrop/Amp High
4 AWG21.15 mm²85 A34.05 V (16.37%)173.9 V56.17 V (27.01%)25067.4 WDrop/Amp High
3 AWG26.67 mm²100 A27.01 V (12.98%)181.0 V44.55 V (21.42%)19879.1 WDrop/Amp High
2 AWG33.62 mm²115 A21.42 V (10.3%)186.6 V35.34 V (16.99%)15769.6 WDrop/Amp High
1 AWG42.41 mm²130 A16.98 V (8.16%)191.0 V28.01 V (13.47%)12501.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.46 V (6.47%)194.5 V22.21 V (10.68%)9911.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.68 V (5.14%)197.3 V17.62 V (8.47%)7862.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.47 V (4.07%)199.5 V13.98 V (6.72%)6236.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.72 V (3.23%)201.3 V11.08 V (5.33%)4945.7 WDrop/Amp High
250 kcmil126.7 mm²255 A5.68 V (2.73%)202.3 V9.38 V (4.51%)4184.5 WDrop/Amp High
300 kcmil152.0 mm²285 A4.74 V (2.28%)203.3 V7.82 V (3.76%)3488.0 WDrop/Amp High
350 kcmil177.3 mm²310 A4.06 V (1.95%)203.9 V6.7 V (3.22%)2990.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.55 V (1.71%)204.4 V5.86 V (2.82%)2615.6 WDrop/Amp High
500 kcmil253.4 mm²380 A2.84 V (1.37%)205.2 V4.69 V (2.25%)2092.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.37 V (1.14%)205.6 V3.91 V (1.88%)1744.0 WDrop/Amp High
750 kcmil380.0 mm²475 A1.9 V (0.91%)206.1 V3.13 V (1.5%)1395.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.42 V (0.68%)206.6 V2.34 V (1.13%)1046.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 150 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 150 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.9V (0.91%) and delivers 206.1V at the load.

What size aluminum wire is required for 425 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.34V (1.13%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.