🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 40 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.24%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.63V (0.3%)
Voltage at Load End207.5 VLoss: 0.51 V (372.1 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 40 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A92.34 V (44.39%)115.7 V152.31 V (73.23%)67971.1 WDrop/Amp High
12 AWG3.31 mm²20 A58.02 V (27.9%)150.0 V95.71 V (46.02%)42713.0 WDrop/Amp High
10 AWG5.26 mm²30 A36.51 V (17.55%)171.5 V60.23 V (28.96%)26878.3 WDrop/Amp High
8 AWG8.37 mm²50 A22.95 V (11.03%)185.1 V37.85 V (18.2%)16891.3 WDrop/Amp High
6 AWG13.3 mm²65 A14.44 V (6.94%)193.6 V23.82 V (11.45%)10630.1 WDrop/Amp High
4 AWG21.15 mm²85 A9.08 V (4.37%)198.9 V14.98 V (7.2%)6684.6 WDrop/Amp High
3 AWG26.67 mm²100 A7.2 V (3.46%)200.8 V11.88 V (5.71%)5301.1 WDrop/Amp High
2 AWG33.62 mm²115 A5.71 V (2.75%)202.3 V9.42 V (4.53%)4205.2 WDrop/Amp High
1 AWG42.41 mm²130 A4.53 V (2.18%)203.5 V7.47 V (3.59%)3333.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.59 V (1.73%)204.4 V5.92 V (2.85%)2643.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.85 V (1.37%)205.2 V4.7 V (2.26%)2096.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.26 V (1.09%)205.7 V3.73 V (1.79%)1663.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.79 V (0.86%)206.2 V2.96 V (1.42%)1318.8 WDrop/Amp High
250 kcmil126.7 mm²255 A1.52 V (0.73%)206.5 V2.5 V (1.2%)1115.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.26 V (0.61%)206.7 V2.08 V (1.0%)930.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.08 V (0.52%)206.9 V1.79 V (0.86%)797.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.95 V (0.46%)207.1 V1.56 V (0.75%)697.5 WDrop/Amp High
500 kcmil253.4 mm²380 A0.76 V (0.36%)207.2 V1.25 V (0.6%)557.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.63 V (0.3%)207.4 V1.04 V (0.5%)465.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.51 V (0.24%)207.5 V0.83 V (0.4%)372.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.38 V (0.18%)207.6 V0.63 V (0.3%)279.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 40 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 40 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.51V (0.24%) and delivers 207.5V at the load.

What size aluminum wire is required for 425 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.63V (0.3%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.