⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 80 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.49%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.25V (0.6%)
Voltage at Load End207.0 VLoss: 1.01 V (744.1 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 80 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A184.67 V (88.79%)23.3 V304.63 V (146.45%)135942.3 WDrop/Amp High
12 AWG3.31 mm²20 A116.05 V (55.79%)92.0 V191.43 V (92.03%)85426.0 WDrop/Amp High
10 AWG5.26 mm²30 A73.03 V (35.11%)135.0 V120.46 V (57.91%)53756.6 WDrop/Amp High
8 AWG8.37 mm²50 A45.89 V (22.06%)162.1 V75.7 V (36.39%)33782.5 WDrop/Amp High
6 AWG13.3 mm²65 A28.88 V (13.89%)179.1 V47.64 V (22.9%)21260.1 WDrop/Amp High
4 AWG21.15 mm²85 A18.16 V (8.73%)189.8 V29.96 V (14.4%)13369.3 WDrop/Amp High
3 AWG26.67 mm²100 A14.4 V (6.92%)193.6 V23.76 V (11.42%)10602.2 WDrop/Amp High
2 AWG33.62 mm²115 A11.43 V (5.49%)196.6 V18.85 V (9.06%)8410.5 WDrop/Amp High
1 AWG42.41 mm²130 A9.06 V (4.35%)198.9 V14.94 V (7.18%)6667.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.18 V (3.45%)200.8 V11.85 V (5.69%)5286.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.7 V (2.74%)202.3 V9.4 V (4.52%)4193.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.52 V (2.17%)203.5 V7.45 V (3.58%)3326.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.58 V (1.72%)204.4 V5.91 V (2.84%)2637.7 WDrop/Amp High
250 kcmil126.7 mm²255 A3.03 V (1.46%)205.0 V5.0 V (2.4%)2231.7 WDrop/Amp High
300 kcmil152.0 mm²285 A2.53 V (1.21%)205.5 V4.17 V (2.0%)1860.3 WDrop/Amp High
350 kcmil177.3 mm²310 A2.17 V (1.04%)205.8 V3.57 V (1.72%)1594.8 WDrop/Amp High
400 kcmil202.7 mm²335 A1.9 V (0.91%)206.1 V3.13 V (1.5%)1395.0 WDrop/Amp High
500 kcmil253.4 mm²380 A1.52 V (0.73%)206.5 V2.5 V (1.2%)1115.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.26 V (0.61%)206.7 V2.08 V (1.0%)930.1 WDrop/Amp High
750 kcmil380.0 mm²475 A1.01 V (0.49%)207.0 V1.67 V (0.8%)744.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.76 V (0.36%)207.2 V1.25 V (0.6%)558.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 80 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 80 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.01V (0.49%) and delivers 207.0V at the load.

What size aluminum wire is required for 425 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.25V (0.6%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.