🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 50 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.3%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.78V (0.38%)
Voltage at Load End207.4 VLoss: 0.63 V (465.1 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 50 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A115.42 V (55.49%)92.6 V190.39 V (91.53%)84963.9 WDrop/Amp High
12 AWG3.31 mm²20 A72.53 V (34.87%)135.5 V119.64 V (57.52%)53391.2 WDrop/Amp High
10 AWG5.26 mm²30 A45.64 V (21.94%)162.4 V75.29 V (36.2%)33597.9 WDrop/Amp High
8 AWG8.37 mm²50 A28.68 V (13.79%)179.3 V47.31 V (22.75%)21114.1 WDrop/Amp High
6 AWG13.3 mm²65 A18.05 V (8.68%)189.9 V29.78 V (14.32%)13287.6 WDrop/Amp High
4 AWG21.15 mm²85 A11.35 V (5.46%)196.6 V18.72 V (9.0%)8355.8 WDrop/Amp High
3 AWG26.67 mm²100 A9.0 V (4.33%)199.0 V14.85 V (7.14%)6626.4 WDrop/Amp High
2 AWG33.62 mm²115 A7.14 V (3.43%)200.9 V11.78 V (5.66%)5256.5 WDrop/Amp High
1 AWG42.41 mm²130 A5.66 V (2.72%)202.3 V9.34 V (4.49%)4167.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.49 V (2.16%)203.5 V7.4 V (3.56%)3303.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.56 V (1.71%)204.4 V5.87 V (2.82%)2620.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.82 V (1.36%)205.2 V4.66 V (2.24%)2078.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.24 V (1.08%)205.8 V3.69 V (1.78%)1648.6 WDrop/Amp High
250 kcmil126.7 mm²255 A1.89 V (0.91%)206.1 V3.13 V (1.5%)1394.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.58 V (0.76%)206.4 V2.61 V (1.25%)1162.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.35 V (0.65%)206.6 V2.23 V (1.07%)996.8 WDrop/Amp High
400 kcmil202.7 mm²335 A1.18 V (0.57%)206.8 V1.95 V (0.94%)871.9 WDrop/Amp High
500 kcmil253.4 mm²380 A0.95 V (0.46%)207.1 V1.56 V (0.75%)697.4 WDrop/Amp High
600 kcmil304.0 mm²420 A0.79 V (0.38%)207.2 V1.3 V (0.63%)581.3 WDrop/Amp High
750 kcmil380.0 mm²475 A0.63 V (0.3%)207.4 V1.04 V (0.5%)465.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.47 V (0.23%)207.5 V0.78 V (0.38%)348.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 50 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 50 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.63V (0.3%) and delivers 207.4V at the load.

What size aluminum wire is required for 425 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.78V (0.38%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.