🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 30 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.47V (0.23%)
Voltage at Load End207.6 VLoss: 0.38 V (279.0 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 30 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A69.25 V (33.29%)138.7 V114.23 V (54.92%)50978.3 WDrop/Amp High
12 AWG3.31 mm²20 A43.52 V (20.92%)164.5 V71.78 V (34.51%)32034.7 WDrop/Amp High
10 AWG5.26 mm²30 A27.39 V (13.17%)180.6 V45.17 V (21.72%)20158.7 WDrop/Amp High
8 AWG8.37 mm²50 A17.21 V (8.27%)190.8 V28.39 V (13.65%)12668.5 WDrop/Amp High
6 AWG13.3 mm²65 A10.83 V (5.21%)197.2 V17.87 V (8.59%)7972.6 WDrop/Amp High
4 AWG21.15 mm²85 A6.81 V (3.27%)201.2 V11.23 V (5.4%)5013.5 WDrop/Amp High
3 AWG26.67 mm²100 A5.4 V (2.6%)202.6 V8.91 V (4.28%)3975.8 WDrop/Amp High
2 AWG33.62 mm²115 A4.28 V (2.06%)203.7 V7.07 V (3.4%)3153.9 WDrop/Amp High
1 AWG42.41 mm²130 A3.4 V (1.63%)204.6 V5.6 V (2.69%)2500.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.69 V (1.29%)205.3 V4.44 V (2.14%)1982.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.14 V (1.03%)205.9 V3.52 V (1.69%)1572.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.69 V (0.81%)206.3 V2.8 V (1.34%)1247.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.34 V (0.65%)206.7 V2.22 V (1.07%)989.1 WDrop/Amp High
250 kcmil126.7 mm²255 A1.14 V (0.55%)206.9 V1.88 V (0.9%)836.9 WDrop/Amp High
300 kcmil152.0 mm²285 A0.95 V (0.46%)207.1 V1.56 V (0.75%)697.6 WDrop/Amp High
350 kcmil177.3 mm²310 A0.81 V (0.39%)207.2 V1.34 V (0.64%)598.1 WDrop/Amp High
400 kcmil202.7 mm²335 A0.71 V (0.34%)207.3 V1.17 V (0.56%)523.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.57 V (0.27%)207.4 V0.94 V (0.45%)418.4 WDrop/Amp High
600 kcmil304.0 mm²420 A0.47 V (0.23%)207.5 V0.78 V (0.38%)348.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.38 V (0.18%)207.6 V0.63 V (0.3%)279.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.28 V (0.14%)207.7 V0.47 V (0.23%)209.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 30 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 30 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.38V (0.18%) and delivers 207.6V at the load.

What size aluminum wire is required for 425 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.47V (0.23%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.