🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 100 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.56V (0.75%)
Voltage at Load End206.7 VLoss: 1.26 V (930.1 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 100 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A230.84 V (110.98%)0.0 V380.78 V (183.07%)169927.8 WDrop/Amp High
12 AWG3.31 mm²20 A145.06 V (69.74%)62.9 V239.28 V (115.04%)106782.4 WDrop/Amp High
10 AWG5.26 mm²30 A91.28 V (43.89%)116.7 V150.58 V (72.39%)67195.8 WDrop/Amp High
8 AWG8.37 mm²50 A57.37 V (27.58%)150.6 V94.63 V (45.49%)42228.2 WDrop/Amp High
6 AWG13.3 mm²65 A36.1 V (17.36%)171.9 V59.55 V (28.63%)26575.2 WDrop/Amp High
4 AWG21.15 mm²85 A22.7 V (10.91%)185.3 V37.45 V (18.0%)16711.6 WDrop/Amp High
3 AWG26.67 mm²100 A18.0 V (8.66%)190.0 V29.7 V (14.28%)13252.7 WDrop/Amp High
2 AWG33.62 mm²115 A14.28 V (6.87%)193.7 V23.56 V (11.33%)10513.1 WDrop/Amp High
1 AWG42.41 mm²130 A11.32 V (5.44%)196.7 V18.68 V (8.98%)8334.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.98 V (4.32%)199.0 V14.81 V (7.12%)6607.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.12 V (3.42%)200.9 V11.75 V (5.65%)5241.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.65 V (2.72%)202.4 V9.32 V (4.48%)4157.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.48 V (2.15%)203.5 V7.39 V (3.55%)3297.1 WDrop/Amp High
250 kcmil126.7 mm²255 A3.79 V (1.82%)204.2 V6.25 V (3.01%)2789.7 WDrop/Amp High
300 kcmil152.0 mm²285 A3.16 V (1.52%)204.8 V5.21 V (2.51%)2325.3 WDrop/Amp High
350 kcmil177.3 mm²310 A2.71 V (1.3%)205.3 V4.47 V (2.15%)1993.5 WDrop/Amp High
400 kcmil202.7 mm²335 A2.37 V (1.14%)205.6 V3.91 V (1.88%)1743.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.89 V (0.91%)206.1 V3.13 V (1.5%)1394.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.58 V (0.76%)206.4 V2.61 V (1.25%)1162.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.26 V (0.61%)206.7 V2.08 V (1.0%)930.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.95 V (0.46%)207.1 V1.56 V (0.75%)697.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 100 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 100 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.26V (0.61%) and delivers 206.7V at the load.

What size aluminum wire is required for 425 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.56V (0.75%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.