🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 60 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.36%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.94V (0.45%)
Voltage at Load End207.2 VLoss: 0.76 V (558.1 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 60 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A138.51 V (66.59%)69.5 V228.47 V (109.84%)101956.7 WDrop/Amp High
12 AWG3.31 mm²20 A87.04 V (41.84%)121.0 V143.57 V (69.02%)64069.5 WDrop/Amp High
10 AWG5.26 mm²30 A54.77 V (26.33%)153.2 V90.35 V (43.44%)40317.5 WDrop/Amp High
8 AWG8.37 mm²50 A34.42 V (16.55%)173.6 V56.78 V (27.3%)25336.9 WDrop/Amp High
6 AWG13.3 mm²65 A21.66 V (10.41%)186.3 V35.73 V (17.18%)15945.1 WDrop/Amp High
4 AWG21.15 mm²85 A13.62 V (6.55%)194.4 V22.47 V (10.8%)10026.9 WDrop/Amp High
3 AWG26.67 mm²100 A10.8 V (5.19%)197.2 V17.82 V (8.57%)7951.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.57 V (4.12%)199.4 V14.13 V (6.8%)6307.9 WDrop/Amp High
1 AWG42.41 mm²130 A6.79 V (3.27%)201.2 V11.21 V (5.39%)5000.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.39 V (2.59%)202.6 V8.88 V (4.27%)3964.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.27 V (2.05%)203.7 V7.05 V (3.39%)3145.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.39 V (1.63%)204.6 V5.59 V (2.69%)2494.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.69 V (1.29%)205.3 V4.43 V (2.13%)1978.3 WDrop/Amp High
250 kcmil126.7 mm²255 A2.27 V (1.09%)205.7 V3.75 V (1.8%)1673.8 WDrop/Amp High
300 kcmil152.0 mm²285 A1.9 V (0.91%)206.1 V3.13 V (1.5%)1395.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.62 V (0.78%)206.4 V2.68 V (1.29%)1196.1 WDrop/Amp High
400 kcmil202.7 mm²335 A1.42 V (0.68%)206.6 V2.34 V (1.13%)1046.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.14 V (0.55%)206.9 V1.88 V (0.9%)836.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.95 V (0.46%)207.1 V1.56 V (0.75%)697.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.76 V (0.36%)207.2 V1.25 V (0.6%)558.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.57 V (0.27%)207.4 V0.94 V (0.45%)418.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 60 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 60 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.76V (0.36%) and delivers 207.2V at the load.

What size aluminum wire is required for 425 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.94V (0.45%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.