🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 120 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.73%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.88V (0.9%)
Voltage at Load End206.5 VLoss: 1.52 V (1116.2 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 120 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A277.01 V (133.18%)0.0 V456.94 V (219.68%)203913.4 WDrop/Amp High
12 AWG3.31 mm²20 A174.07 V (83.69%)33.9 V287.14 V (138.05%)128138.9 WDrop/Amp High
10 AWG5.26 mm²30 A109.54 V (52.66%)98.5 V180.69 V (86.87%)80635.0 WDrop/Amp High
8 AWG8.37 mm²50 A68.84 V (33.1%)139.2 V113.55 V (54.59%)50673.8 WDrop/Amp High
6 AWG13.3 mm²65 A43.32 V (20.83%)164.7 V71.46 V (34.36%)31890.2 WDrop/Amp High
4 AWG21.15 mm²85 A27.24 V (13.1%)180.8 V44.94 V (21.6%)20053.9 WDrop/Amp High
3 AWG26.67 mm²100 A21.6 V (10.39%)186.4 V35.64 V (17.13%)15903.3 WDrop/Amp High
2 AWG33.62 mm²115 A17.14 V (8.24%)190.9 V28.27 V (13.59%)12615.7 WDrop/Amp High
1 AWG42.41 mm²130 A13.59 V (6.53%)194.4 V22.41 V (10.77%)10000.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.77 V (5.18%)197.2 V17.77 V (8.54%)7929.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.54 V (4.11%)199.5 V14.1 V (6.78%)6290.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.78 V (3.26%)201.2 V11.18 V (5.38%)4989.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.37 V (2.58%)202.6 V8.87 V (4.26%)3956.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.55 V (2.19%)203.5 V7.5 V (3.61%)3347.6 WDrop/Amp High
300 kcmil152.0 mm²285 A3.79 V (1.82%)204.2 V6.25 V (3.01%)2790.4 WDrop/Amp High
350 kcmil177.3 mm²310 A3.25 V (1.56%)204.8 V5.36 V (2.58%)2392.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.84 V (1.37%)205.2 V4.69 V (2.25%)2092.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.27 V (1.09%)205.7 V3.75 V (1.8%)1673.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.9 V (0.91%)206.1 V3.13 V (1.5%)1395.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.52 V (0.73%)206.5 V2.5 V (1.2%)1116.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.14 V (0.55%)206.9 V1.88 V (0.9%)837.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 120 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 120 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.52V (0.73%) and delivers 206.5V at the load.

What size aluminum wire is required for 425 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.88V (0.9%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.