🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 300 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.82%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.41V (2.26%)
Voltage at Load End235.6 VLoss: 4.38 V (1860.3 W)
Power & Breaker (125%)102.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 300 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A799.66 V (333.19%)0.0 V1319.07 V (549.61%)339855.7 WDrop/Amp High
12 AWG3.31 mm²20 A502.51 V (209.38%)0.0 V828.9 V (345.37%)213564.9 WDrop/Amp High
10 AWG5.26 mm²30 A316.22 V (131.76%)0.0 V521.61 V (217.34%)134391.6 WDrop/Amp High
8 AWG8.37 mm²50 A198.72 V (82.8%)41.3 V327.8 V (136.58%)84456.4 WDrop/Amp High
6 AWG13.3 mm²65 A125.06 V (52.11%)114.9 V206.29 V (85.95%)53150.4 WDrop/Amp High
4 AWG21.15 mm²85 A78.64 V (32.77%)161.4 V129.72 V (54.05%)33423.2 WDrop/Amp High
3 AWG26.67 mm²100 A62.37 V (25.99%)177.6 V102.87 V (42.86%)26505.4 WDrop/Amp High
2 AWG33.62 mm²115 A49.47 V (20.61%)190.5 V81.61 V (34.0%)21026.2 WDrop/Amp High
1 AWG42.41 mm²130 A39.22 V (16.34%)200.8 V64.69 V (26.96%)16668.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.1 V (12.96%)208.9 V51.29 V (21.37%)13215.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.67 V (10.28%)215.3 V40.69 V (16.95%)10483.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.57 V (8.15%)220.4 V32.27 V (13.45%)8315.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.52 V (6.46%)224.5 V25.59 V (10.66%)6594.2 WDrop/Amp High
250 kcmil126.7 mm²255 A13.13 V (5.47%)226.9 V21.65 V (9.02%)5579.3 WDrop/Amp High
300 kcmil152.0 mm²285 A10.94 V (4.56%)229.1 V18.05 V (7.52%)4650.7 WDrop/Amp High
350 kcmil177.3 mm²310 A9.38 V (3.91%)230.6 V15.47 V (6.45%)3987.0 WDrop/Amp High
400 kcmil202.7 mm²335 A8.21 V (3.42%)231.8 V13.54 V (5.64%)3487.4 WDrop/Amp High
500 kcmil253.4 mm²380 A6.56 V (2.73%)233.4 V10.83 V (4.51%)2789.7 WDrop/Amp High
600 kcmil304.0 mm²420 A5.47 V (2.28%)234.5 V9.03 V (3.76%)2325.3 WDrop/Amp High
750 kcmil380.0 mm²475 A4.38 V (1.82%)235.6 V7.22 V (3.01%)1860.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.28 V (1.37%)236.7 V5.41 V (2.26%)1395.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 300 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 300 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 4.38V (1.82%) and delivers 235.6V at the load.

What size aluminum wire is required for 425 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.41V (2.26%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.