⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 500 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.82V (3.26%)
Voltage at Load End233.7 VLoss: 6.32 V (4650.7 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1154.21 V (480.92%)0.0 V1903.91 V (793.29%)849639.2 WDrop/Amp High
12 AWG3.31 mm²20 A725.3 V (302.21%)0.0 V1196.41 V (498.51%)533912.2 WDrop/Amp High
10 AWG5.26 mm²30 A456.42 V (190.17%)0.0 V752.88 V (313.7%)335979.0 WDrop/Amp High
8 AWG8.37 mm²50 A286.83 V (119.51%)0.0 V473.13 V (197.14%)211140.9 WDrop/Amp High
6 AWG13.3 mm²65 A180.51 V (75.21%)59.5 V297.75 V (124.06%)132875.9 WDrop/Amp High
4 AWG21.15 mm²85 A113.51 V (47.3%)126.5 V187.24 V (78.02%)83557.9 WDrop/Amp High
3 AWG26.67 mm²100 A90.02 V (37.51%)150.0 V148.49 V (61.87%)66263.6 WDrop/Amp High
2 AWG33.62 mm²115 A71.41 V (29.75%)168.6 V117.79 V (49.08%)52565.4 WDrop/Amp High
1 AWG42.41 mm²130 A56.61 V (23.59%)183.4 V93.38 V (38.91%)41670.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A44.88 V (18.7%)195.1 V74.03 V (30.85%)33038.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A35.6 V (14.83%)204.4 V58.73 V (24.47%)26208.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A28.24 V (11.77%)211.8 V46.58 V (19.41%)20788.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A22.4 V (9.33%)217.6 V36.94 V (15.39%)16485.5 WDrop/Amp High
250 kcmil126.7 mm²255 A18.95 V (7.9%)221.1 V31.26 V (13.02%)13948.3 WDrop/Amp High
300 kcmil152.0 mm²285 A15.79 V (6.58%)224.2 V26.05 V (10.86%)11626.6 WDrop/Amp High
350 kcmil177.3 mm²310 A13.54 V (5.64%)226.5 V22.34 V (9.31%)9967.6 WDrop/Amp High
400 kcmil202.7 mm²335 A11.84 V (4.93%)228.2 V19.54 V (8.14%)8718.5 WDrop/Amp High
500 kcmil253.4 mm²380 A9.47 V (3.95%)230.5 V15.63 V (6.51%)6974.1 WDrop/Amp High
600 kcmil304.0 mm²420 A7.9 V (3.29%)232.1 V13.03 V (5.43%)5813.3 WDrop/Amp High
750 kcmil380.0 mm²475 A6.32 V (2.63%)233.7 V10.42 V (4.34%)4650.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.74 V (1.97%)235.3 V7.82 V (3.26%)3487.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 500 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.32V (2.63%) and delivers 233.7V at the load.

What size aluminum wire is required for 425 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.82V (3.26%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.