🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 600 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.73%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.38V (4.51%)
Voltage at Load End202.3 VLoss: 5.69 V (4185.3 W)
Power & Breaker (125%)153.11 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 600 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1385.05 V (665.89%)0.0 V2284.69 V (1098.41%)1019567.0 WDrop/Amp High
12 AWG3.31 mm²20 A870.37 V (418.44%)0.0 V1435.7 V (690.24%)640694.7 WDrop/Amp High
10 AWG5.26 mm²30 A547.7 V (263.32%)0.0 V903.45 V (434.35%)403174.8 WDrop/Amp High
8 AWG8.37 mm²50 A344.19 V (165.48%)0.0 V567.76 V (272.96%)253369.1 WDrop/Amp High
6 AWG13.3 mm²65 A216.61 V (104.14%)0.0 V357.3 V (171.78%)159451.1 WDrop/Amp High
4 AWG21.15 mm²85 A136.21 V (65.49%)71.8 V224.69 V (108.02%)100269.5 WDrop/Amp High
3 AWG26.67 mm²100 A108.02 V (51.93%)100.0 V178.18 V (85.67%)79516.3 WDrop/Amp High
2 AWG33.62 mm²115 A85.69 V (41.2%)122.3 V141.35 V (67.96%)63078.5 WDrop/Amp High
1 AWG42.41 mm²130 A67.93 V (32.66%)140.1 V112.05 V (53.87%)50004.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A53.86 V (25.89%)154.1 V88.84 V (42.71%)39646.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A42.72 V (20.54%)165.3 V70.48 V (33.88%)31450.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.89 V (16.29%)174.1 V55.9 V (26.88%)24946.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.87 V (12.92%)181.1 V44.33 V (21.31%)19782.6 WDrop/Amp High
250 kcmil126.7 mm²255 A22.74 V (10.93%)185.3 V37.51 V (18.03%)16738.0 WDrop/Amp High
300 kcmil152.0 mm²285 A18.95 V (9.11%)189.0 V31.26 V (15.03%)13952.0 WDrop/Amp High
350 kcmil177.3 mm²310 A16.25 V (7.81%)191.8 V26.8 V (12.89%)11961.1 WDrop/Amp High
400 kcmil202.7 mm²335 A14.21 V (6.83%)193.8 V23.44 V (11.27%)10462.3 WDrop/Amp High
500 kcmil253.4 mm²380 A11.37 V (5.47%)196.6 V18.75 V (9.02%)8369.0 WDrop/Amp High
600 kcmil304.0 mm²420 A9.48 V (4.56%)198.5 V15.63 V (7.52%)6976.0 WDrop/Amp High
750 kcmil380.0 mm²475 A7.58 V (3.64%)200.4 V12.51 V (6.01%)5580.8 W~ ≤5%
1000 kcmil506.7 mm²545 A5.69 V (2.73%)202.3 V9.38 V (4.51%)4185.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 600 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 600 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.69V (2.73%) and delivers 202.3V at the load.

What size aluminum wire is required for 425 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.38V (4.51%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.