🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 600 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.58%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.38V (1.95%)
Voltage at Load End472.4 VLoss: 7.58 V (5580.8 W)
Power & Breaker (125%)353.34 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 600 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1385.05 V (288.55%)0.0 V2284.69 V (475.98%)1019567.0 WDrop/Amp High
12 AWG3.31 mm²20 A870.37 V (181.33%)0.0 V1435.7 V (299.1%)640694.7 WDrop/Amp High
10 AWG5.26 mm²30 A547.7 V (114.1%)0.0 V903.45 V (188.22%)403174.8 WDrop/Amp High
8 AWG8.37 mm²50 A344.19 V (71.71%)135.8 V567.76 V (118.28%)253369.1 WDrop/Amp High
6 AWG13.3 mm²65 A216.61 V (45.13%)263.4 V357.3 V (74.44%)159451.1 WDrop/Amp High
4 AWG21.15 mm²85 A136.21 V (28.38%)343.8 V224.69 V (46.81%)100269.5 WDrop/Amp High
3 AWG26.67 mm²100 A108.02 V (22.5%)372.0 V178.18 V (37.12%)79516.3 WDrop/Amp High
2 AWG33.62 mm²115 A85.69 V (17.85%)394.3 V141.35 V (29.45%)63078.5 WDrop/Amp High
1 AWG42.41 mm²130 A67.93 V (14.15%)412.1 V112.05 V (23.34%)50004.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A53.86 V (11.22%)426.1 V88.84 V (18.51%)39646.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A42.72 V (8.9%)437.3 V70.48 V (14.68%)31450.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.89 V (7.06%)446.1 V55.9 V (11.65%)24946.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.87 V (5.6%)453.1 V44.33 V (9.24%)19782.6 WDrop/Amp High
250 kcmil126.7 mm²255 A22.74 V (4.74%)457.3 V37.51 V (7.81%)16738.0 WDrop/Amp High
300 kcmil152.0 mm²285 A18.95 V (3.95%)461.0 V31.26 V (6.51%)13952.0 WDrop/Amp High
350 kcmil177.3 mm²310 A16.25 V (3.39%)463.8 V26.8 V (5.58%)11961.1 WDrop/Amp High
400 kcmil202.7 mm²335 A14.21 V (2.96%)465.8 V23.44 V (4.88%)10462.3 WDrop/Amp High
500 kcmil253.4 mm²380 A11.37 V (2.37%)468.6 V18.75 V (3.91%)8369.0 WDrop/Amp High
600 kcmil304.0 mm²420 A9.48 V (1.97%)470.5 V15.63 V (3.26%)6976.0 WDrop/Amp High
750 kcmil380.0 mm²475 A7.58 V (1.58%)472.4 V12.51 V (2.61%)5580.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A5.69 V (1.18%)474.3 V9.38 V (1.95%)4185.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 600 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 600 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 7.58V (1.58%) and delivers 472.4V at the load.

What size aluminum wire is required for 425 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.38V (1.95%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.