🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.98%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 11.76V (2.45%)
Voltage at Load End465.7 VLoss: 14.3 V (1114.3 W)
Power & Breaker (125%)37.41 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A183.32 V (38.19%)296.7 V302.39 V (63.0%)14288.0 WDrop/Amp High
12 AWG3.31 mm²20 A115.2 V (24.0%)364.8 V190.02 V (39.59%)8978.6 WDrop/Amp High
10 AWG5.26 mm²30 A72.49 V (15.1%)407.5 V119.57 V (24.91%)5650.0 WDrop/Amp High
8 AWG8.37 mm²50 A45.56 V (9.49%)434.4 V75.14 V (15.66%)3550.7 WDrop/Amp High
6 AWG13.3 mm²65 A28.67 V (5.97%)451.3 V47.29 V (9.85%)2234.5 WDrop/Amp High
4 AWG21.15 mm²85 A18.03 V (3.76%)462.0 V29.74 V (6.2%)1405.2 W~ ≤5%
3 AWG26.67 mm²100 A14.3 V (2.98%)465.7 V23.58 V (4.91%)1114.3 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A11.34 V (2.36%)468.7 V18.71 V (3.9%)884.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A8.99 V (1.87%)471.0 V14.83 V (3.09%)700.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A7.13 V (1.49%)472.9 V11.76 V (2.45%)555.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A5.65 V (1.18%)474.3 V9.33 V (1.94%)440.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.49 V (0.93%)475.5 V7.4 V (1.54%)349.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.56 V (0.74%)476.4 V5.87 V (1.22%)277.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.01 V (0.63%)477.0 V4.96 V (1.03%)234.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.51 V (0.52%)477.5 V4.14 V (0.86%)195.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.15 V (0.45%)477.8 V3.55 V (0.74%)167.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.88 V (0.39%)478.1 V3.1 V (0.65%)146.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.5 V (0.31%)478.5 V2.48 V (0.52%)117.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.25 V (0.26%)478.7 V2.07 V (0.43%)97.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.0 V (0.21%)479.0 V1.66 V (0.34%)78.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.75 V (0.16%)479.2 V1.24 V (0.26%)58.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 750 feet one-way at 480V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 14.3V (2.98%) and delivers 465.7V at the load.

What size aluminum wire is required for 45 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 11.76V (2.45%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.