⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

45 Amp Wire Size at 800 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 45 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)300 kcmil152.0 mm² · Drop: 2.57%
Aluminum Wire (≤3% Drop)500 kcmilDrop: 3.06V (2.55%)
Voltage at Load End116.9 VLoss: 3.09 V (139.0 W)
Power & Breaker (125%)5.4 kW60A Breaker Recommended

All AWG & kcmil Wire Gauges for 45 Amps at 800 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A225.79 V (188.16%)0.0 V372.44 V (310.37%)10160.4 WDrop/Amp High
12 AWG3.31 mm²20 A141.88 V (118.24%)0.0 V234.04 V (195.04%)6384.8 WDrop/Amp High
10 AWG5.26 mm²30 A89.28 V (74.4%)30.7 V147.28 V (122.73%)4017.8 WDrop/Amp High
8 AWG8.37 mm²50 A56.11 V (46.76%)63.9 V92.55 V (77.13%)2524.9 WDrop/Amp High
6 AWG13.3 mm²65 A35.31 V (29.43%)84.7 V58.25 V (48.54%)1589.0 WDrop/Amp High
4 AWG21.15 mm²85 A22.21 V (18.5%)97.8 V36.63 V (30.52%)999.2 WDrop/Amp High
3 AWG26.67 mm²100 A17.61 V (14.67%)102.4 V29.05 V (24.21%)792.4 WDrop/Amp High
2 AWG33.62 mm²115 A13.97 V (11.64%)106.0 V23.04 V (19.2%)628.6 WDrop/Amp High
1 AWG42.41 mm²130 A11.07 V (9.23%)108.9 V18.27 V (15.22%)498.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.78 V (7.32%)111.2 V14.48 V (12.07%)395.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.96 V (5.8%)113.0 V11.49 V (9.57%)313.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.52 V (4.6%)114.5 V9.11 V (7.59%)248.6 W~ ≤5%
4/0 AWG107.2 mm²230 A4.38 V (3.65%)115.6 V7.23 V (6.02%)197.1 W~ ≤5%
250 kcmil126.7 mm²255 A3.71 V (3.09%)116.3 V6.11 V (5.1%)166.8 W~ ≤5%
300 kcmil152.0 mm²285 A3.09 V (2.57%)116.9 V5.1 V (4.25%)139.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.65 V (2.21%)117.4 V4.37 V (3.64%)119.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.32 V (1.93%)117.7 V3.82 V (3.18%)104.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.85 V (1.54%)118.1 V3.06 V (2.55%)83.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.54 V (1.29%)118.5 V2.55 V (2.12%)69.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.24 V (1.03%)118.8 V2.04 V (1.7%)55.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.93 V (0.77%)119.1 V1.53 V (1.27%)41.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 45 amps at 800 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 45A load over 800 feet one-way at 120V (1-Phase), you need 300 kcmil copper wire. This produces a voltage drop of 3.09V (2.57%) and delivers 116.9V at the load.

What size aluminum wire is required for 45 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 500 kcmil to maintain voltage drop at 3.06V (2.55%).

What breaker size is needed for a 45A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (45A × 1.25 = 56.2A), which corresponds to a standard 60A circuit breaker.