🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 250 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.7%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.04V (2.1%)
Voltage at Load End235.9 VLoss: 4.08 V (1936.4 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 250 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A744.78 V (310.33%)0.0 V1228.54 V (511.89%)353771.3 WDrop/Amp High
12 AWG3.31 mm²20 A468.02 V (195.01%)0.0 V772.01 V (321.67%)222309.5 WDrop/Amp High
10 AWG5.26 mm²30 A294.51 V (122.71%)0.0 V485.81 V (202.42%)139894.4 WDrop/Amp High
8 AWG8.37 mm²50 A185.08 V (77.12%)54.9 V305.3 V (127.21%)87914.5 WDrop/Amp High
6 AWG13.3 mm²65 A116.48 V (48.53%)123.5 V192.13 V (80.06%)55326.6 WDrop/Amp High
4 AWG21.15 mm²85 A73.25 V (30.52%)166.8 V120.82 V (50.34%)34791.7 WDrop/Amp High
3 AWG26.67 mm²100 A58.09 V (24.2%)181.9 V95.81 V (39.92%)27590.7 WDrop/Amp High
2 AWG33.62 mm²115 A46.08 V (19.2%)193.9 V76.01 V (31.67%)21887.1 WDrop/Amp High
1 AWG42.41 mm²130 A36.53 V (15.22%)203.5 V60.25 V (25.11%)17350.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A28.96 V (12.07%)211.0 V47.77 V (19.91%)13756.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.97 V (9.57%)217.0 V37.9 V (15.79%)10912.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.22 V (7.59%)221.8 V30.06 V (12.52%)8656.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.45 V (6.02%)225.5 V23.84 V (9.93%)6864.2 WDrop/Amp High
250 kcmil126.7 mm²255 A12.23 V (5.09%)227.8 V20.17 V (8.4%)5807.8 WDrop/Amp High
300 kcmil152.0 mm²285 A10.19 V (4.25%)229.8 V16.81 V (7.0%)4841.1 WDrop/Amp High
350 kcmil177.3 mm²310 A8.74 V (3.64%)231.3 V14.41 V (6.01%)4150.3 WDrop/Amp High
400 kcmil202.7 mm²335 A7.64 V (3.18%)232.4 V12.61 V (5.25%)3630.2 WDrop/Amp High
500 kcmil253.4 mm²380 A6.11 V (2.55%)233.9 V10.08 V (4.2%)2903.9 WDrop/Amp High
600 kcmil304.0 mm²420 A5.1 V (2.12%)234.9 V8.41 V (3.5%)2420.5 WDrop/Amp High
750 kcmil380.0 mm²475 A4.08 V (1.7%)235.9 V6.72 V (2.8%)1936.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.06 V (1.27%)236.9 V5.04 V (2.1%)1452.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 250 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 250 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 4.08V (1.7%) and delivers 235.9V at the load.

What size aluminum wire is required for 475 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.04V (2.1%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.