🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)10× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.55V (46.23%)
Voltage at Load End11.7 VLoss: 0.34 V (159.8 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A819.26 V (6827.17%)0.0 V1351.4 V (11261.63%)389148.5 WDrop/Amp High
12 AWG3.31 mm²20 A514.82 V (4290.18%)0.0 V849.22 V (7076.8%)244540.4 WDrop/Amp High
10 AWG5.26 mm²30 A323.97 V (2699.72%)0.0 V534.39 V (4453.27%)153883.8 WDrop/Amp High
8 AWG8.37 mm²50 A203.59 V (1696.6%)0.0 V335.83 V (2798.59%)96705.9 WDrop/Amp High
6 AWG13.3 mm²65 A128.12 V (1067.71%)0.0 V211.35 V (1761.22%)60859.3 WDrop/Amp High
4 AWG21.15 mm²85 A80.57 V (671.42%)0.0 V132.9 V (1107.53%)38270.9 WDrop/Amp High
3 AWG26.67 mm²100 A63.89 V (532.45%)0.0 V105.4 V (878.3%)30349.8 WDrop/Amp High
2 AWG33.62 mm²115 A50.69 V (422.38%)0.0 V83.61 V (696.73%)24075.8 WDrop/Amp High
1 AWG42.41 mm²130 A40.18 V (334.84%)0.0 V66.28 V (552.33%)19085.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A31.86 V (265.48%)0.0 V52.55 V (437.92%)15132.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A25.27 V (210.6%)0.0 V41.69 V (347.39%)12004.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A20.05 V (167.05%)0.0 V33.07 V (275.55%)9521.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.9 V (132.47%)0.0 V26.22 V (218.51%)7550.6 WDrop/Amp High
250 kcmil126.7 mm²255 A13.45 V (112.08%)0.0 V22.19 V (184.88%)6388.5 WDrop/Amp High
300 kcmil152.0 mm²285 A11.21 V (93.42%)0.8 V18.49 V (154.11%)5325.2 WDrop/Amp High
350 kcmil177.3 mm²310 A9.61 V (80.09%)2.4 V15.85 V (132.12%)4565.3 WDrop/Amp High
400 kcmil202.7 mm²335 A8.41 V (70.06%)3.6 V13.87 V (115.56%)3993.2 WDrop/Amp High
500 kcmil253.4 mm²380 A6.72 V (56.04%)5.3 V11.09 V (92.44%)3194.3 WDrop/Amp High
600 kcmil304.0 mm²420 A5.61 V (46.71%)6.4 V9.25 V (77.05%)2662.6 WDrop/Amp High
750 kcmil380.0 mm²475 A4.48 V (37.37%)7.5 V7.4 V (61.64%)2130.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.36 V (28.03%)8.6 V5.55 V (46.23%)1597.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 275 feet one-way at 12V (DC), you need 10× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.8%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.55V (46.23%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.