⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.87%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.8V (2.31%)
Voltage at Load End204.1 VLoss: 3.88 V (3195.1 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A709.5 V (341.11%)0.0 V1170.34 V (562.67%)583722.7 WDrop/Amp High
12 AWG3.31 mm²20 A445.85 V (214.35%)0.0 V735.44 V (353.58%)366810.6 WDrop/Amp High
10 AWG5.26 mm²30 A280.56 V (134.89%)0.0 V462.8 V (222.5%)230825.7 WDrop/Amp High
8 AWG8.37 mm²50 A176.32 V (84.77%)31.7 V290.84 V (139.83%)145058.9 WDrop/Amp High
6 AWG13.3 mm²65 A110.96 V (53.35%)97.0 V183.03 V (88.0%)91289.0 WDrop/Amp High
4 AWG21.15 mm²85 A69.78 V (33.55%)138.2 V115.1 V (55.34%)57406.3 WDrop/Amp High
3 AWG26.67 mm²100 A55.33 V (26.6%)152.7 V91.28 V (43.88%)45524.7 WDrop/Amp High
2 AWG33.62 mm²115 A43.9 V (21.1%)164.1 V72.41 V (34.81%)36113.7 WDrop/Amp High
1 AWG42.41 mm²130 A34.8 V (16.73%)173.2 V57.4 V (27.6%)28628.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.59 V (13.26%)180.4 V45.51 V (21.88%)22698.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A21.89 V (10.52%)186.1 V36.1 V (17.36%)18006.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.36 V (8.35%)190.6 V28.64 V (13.77%)14282.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.77 V (6.62%)194.2 V22.71 V (10.92%)11326.0 WDrop/Amp High
250 kcmil126.7 mm²255 A11.65 V (5.6%)196.4 V19.21 V (9.24%)9582.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.71 V (4.67%)198.3 V16.02 V (7.7%)7987.8 WDrop/Amp High
350 kcmil177.3 mm²310 A8.32 V (4.0%)199.7 V13.73 V (6.6%)6848.0 WDrop/Amp High
400 kcmil202.7 mm²335 A7.28 V (3.5%)200.7 V12.01 V (5.77%)5989.9 WDrop/Amp High
500 kcmil253.4 mm²380 A5.82 V (2.8%)202.2 V9.61 V (4.62%)4791.4 WDrop/Amp High
600 kcmil304.0 mm²420 A4.85 V (2.33%)203.1 V8.01 V (3.85%)3993.9 WDrop/Amp High
750 kcmil380.0 mm²475 A3.88 V (1.87%)204.1 V6.41 V (3.08%)3195.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.91 V (1.4%)205.1 V4.8 V (2.31%)2396.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 275 feet one-way at 208V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.88V (1.87%) and delivers 204.1V at the load.

What size aluminum wire is required for 475 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.8V (2.31%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.