🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.53%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.1V (5.04%)
Voltage at Load End236.3 VLoss: 3.67 V (1742.7 W)
Power & Breaker (125%)114.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1787.48 V (744.78%)0.0 V2948.5 V (1228.54%)849051.2 WDrop/Amp High
12 AWG3.31 mm²20 A1123.25 V (468.02%)0.0 V1852.83 V (772.01%)533542.7 WDrop/Amp High
10 AWG5.26 mm²30 A706.83 V (294.51%)0.0 V1165.95 V (485.81%)335746.5 WDrop/Amp High
8 AWG8.37 mm²50 A444.2 V (185.08%)0.0 V732.72 V (305.3%)210994.8 WDrop/Amp High
6 AWG13.3 mm²65 A279.55 V (116.48%)0.0 V461.12 V (192.13%)132783.9 WDrop/Amp High
4 AWG21.15 mm²85 A175.79 V (73.25%)64.2 V289.97 V (120.82%)83500.1 WDrop/Amp High
3 AWG26.67 mm²100 A139.41 V (58.09%)100.6 V229.95 V (95.81%)66217.7 WDrop/Amp High
2 AWG33.62 mm²115 A110.59 V (46.08%)129.4 V182.42 V (76.01%)52529.0 WDrop/Amp High
1 AWG42.41 mm²130 A87.67 V (36.53%)152.3 V144.61 V (60.25%)41641.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A69.51 V (28.96%)170.5 V114.65 V (47.77%)33016.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A55.14 V (22.97%)184.9 V90.95 V (37.9%)26190.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A43.74 V (18.22%)196.3 V72.14 V (30.06%)20774.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A34.68 V (14.45%)205.3 V57.21 V (23.84%)16474.1 WDrop/Amp High
250 kcmil126.7 mm²255 A29.34 V (12.23%)210.7 V48.4 V (20.17%)13938.6 WDrop/Amp High
300 kcmil152.0 mm²285 A24.46 V (10.19%)215.5 V40.35 V (16.81%)11618.6 WDrop/Amp High
350 kcmil177.3 mm²310 A20.97 V (8.74%)219.0 V34.59 V (14.41%)9960.7 WDrop/Amp High
400 kcmil202.7 mm²335 A18.34 V (7.64%)221.7 V30.26 V (12.61%)8712.5 WDrop/Amp High
500 kcmil253.4 mm²380 A14.67 V (6.11%)225.3 V24.2 V (10.08%)6969.3 WDrop/Amp High
600 kcmil304.0 mm²420 A12.23 V (5.1%)227.8 V20.17 V (8.41%)5809.3 WDrop/Amp High
750 kcmil380.0 mm²475 A9.78 V (4.08%)230.2 V16.14 V (6.72%)4647.4 W~ ≤5%
1000 kcmil506.7 mm²545 A7.34 V (3.06%)232.7 V12.1 V (5.04%)3485.3 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 600 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.67V (1.53%) and delivers 236.3V at the load.

What size aluminum wire is required for 475 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.1V (5.04%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.