🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.04%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.18V (6.74%)
Voltage at Load End235.1 VLoss: 4.91 V (4672.9 W)
Power & Breaker (125%)228.63 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2389.89 V (995.79%)0.0 V3942.21 V (1642.59%)2276680.2 WDrop/Amp High
12 AWG3.31 mm²20 A1501.81 V (625.75%)0.0 V2477.28 V (1032.2%)1430663.1 WDrop/Amp High
10 AWG5.26 mm²30 A945.05 V (393.77%)0.0 V1558.9 V (649.54%)900284.2 WDrop/Amp High
8 AWG8.37 mm²50 A593.9 V (247.46%)0.0 V979.66 V (408.19%)565770.0 WDrop/Amp High
6 AWG13.3 mm²65 A373.76 V (155.73%)0.0 V616.53 V (256.89%)356052.2 WDrop/Amp High
4 AWG21.15 mm²85 A235.03 V (97.93%)5.0 V387.7 V (161.54%)223900.5 WDrop/Amp High
3 AWG26.67 mm²100 A186.39 V (77.66%)53.6 V307.45 V (128.11%)177558.9 WDrop/Amp High
2 AWG33.62 mm²115 A147.86 V (61.61%)92.1 V243.9 V (101.62%)140853.5 WDrop/Amp High
1 AWG42.41 mm²130 A117.21 V (48.84%)122.8 V193.35 V (80.56%)111659.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A92.93 V (38.72%)147.1 V153.3 V (63.87%)88530.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A73.72 V (30.72%)166.3 V121.6 V (50.67%)70228.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A58.48 V (24.36%)181.5 V96.46 V (40.19%)55705.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A46.37 V (19.32%)193.6 V76.49 V (31.87%)44174.4 WDrop/Amp High
250 kcmil126.7 mm²255 A39.23 V (16.35%)200.8 V64.72 V (26.97%)37375.6 WDrop/Amp High
300 kcmil152.0 mm²285 A32.7 V (13.63%)207.3 V53.95 V (22.48%)31154.6 WDrop/Amp High
350 kcmil177.3 mm²310 A28.04 V (11.68%)212.0 V46.25 V (19.27%)26708.9 WDrop/Amp High
400 kcmil202.7 mm²335 A24.52 V (10.22%)215.5 V40.45 V (16.86%)23362.1 WDrop/Amp High
500 kcmil253.4 mm²380 A19.62 V (8.17%)220.4 V32.36 V (13.48%)18687.8 WDrop/Amp High
600 kcmil304.0 mm²420 A16.35 V (6.81%)223.6 V26.97 V (11.24%)15577.3 WDrop/Amp High
750 kcmil380.0 mm²475 A13.08 V (5.45%)226.9 V21.58 V (8.99%)12461.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.81 V (4.09%)230.2 V16.18 V (6.74%)9345.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 800 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.91V (2.04%) and delivers 235.1V at the load.

What size aluminum wire is required for 550 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.18V (6.74%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.