🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 600 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)31× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.91%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.84V (148.64%)
Voltage at Load End11.7 VLoss: 0.35 V (244.2 W)
Power & Breaker (125%)8.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 600 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2634.18 V (21951.46%)0.0 V4345.16 V (36209.65%)1843922.8 WDrop/Amp High
12 AWG3.31 mm²20 A1655.31 V (13794.27%)0.0 V2730.49 V (22754.1%)1158718.8 WDrop/Amp High
10 AWG5.26 mm²30 A1041.65 V (8680.43%)0.0 V1718.24 V (14318.65%)729155.8 WDrop/Amp High
8 AWG8.37 mm²50 A654.61 V (5455.08%)0.0 V1079.8 V (8998.34%)458226.9 WDrop/Amp High
6 AWG13.3 mm²65 A411.96 V (3433.01%)0.0 V679.54 V (5662.86%)288372.9 WDrop/Amp High
4 AWG21.15 mm²85 A259.06 V (2158.82%)0.0 V427.33 V (3561.04%)181340.9 WDrop/Amp High
3 AWG26.67 mm²100 A205.44 V (1712.0%)0.0 V338.88 V (2824.0%)143808.0 WDrop/Amp High
2 AWG33.62 mm²115 A162.97 V (1358.09%)0.0 V268.83 V (2240.22%)114079.7 WDrop/Amp High
1 AWG42.41 mm²130 A129.19 V (1076.61%)0.0 V213.11 V (1775.9%)90435.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A102.43 V (853.6%)0.0 V168.96 V (1408.04%)71702.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A81.26 V (677.13%)0.0 V134.03 V (1116.95%)56879.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A64.45 V (537.1%)0.0 V106.32 V (885.97%)45116.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A51.11 V (425.92%)0.0 V84.31 V (702.58%)35777.6 WDrop/Amp High
250 kcmil126.7 mm²255 A43.24 V (360.37%)0.0 V71.33 V (594.44%)30271.2 WDrop/Amp High
300 kcmil152.0 mm²285 A36.05 V (300.39%)0.0 V59.46 V (495.5%)25232.6 WDrop/Amp High
350 kcmil177.3 mm²310 A30.9 V (257.52%)0.0 V50.98 V (424.79%)21632.0 WDrop/Amp High
400 kcmil202.7 mm²335 A27.03 V (225.25%)0.0 V44.59 V (371.56%)18921.4 WDrop/Amp High
500 kcmil253.4 mm²380 A21.62 V (180.19%)0.0 V35.67 V (297.22%)15135.6 WDrop/Amp High
600 kcmil304.0 mm²420 A18.02 V (150.19%)0.0 V29.73 V (247.75%)12616.3 WDrop/Amp High
750 kcmil380.0 mm²475 A14.42 V (120.16%)0.0 V23.78 V (198.2%)10093.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.81 V (90.11%)1.2 V17.84 V (148.64%)7569.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 600 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 600 feet one-way at 12V (DC), you need 31× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.91%) and delivers 11.7V at the load.

What size aluminum wire is required for 700 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.84V (148.64%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.