🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 200 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.62V (1.38%)
Voltage at Load End478.0 VLoss: 2.0 V (3128.2 W)
Power & Breaker (125%)748.25 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 200 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A977.68 V (203.68%)0.0 V1612.72 V (335.98%)1524058.6 WDrop/Amp High
12 AWG3.31 mm²20 A614.38 V (127.99%)0.0 V1013.43 V (211.13%)957716.6 WDrop/Amp High
10 AWG5.26 mm²30 A386.61 V (80.54%)93.4 V637.73 V (132.86%)602669.6 WDrop/Amp High
8 AWG8.37 mm²50 A242.96 V (50.62%)237.0 V400.77 V (83.49%)378738.6 WDrop/Amp High
6 AWG13.3 mm²65 A152.9 V (31.85%)327.1 V252.22 V (52.54%)238349.0 WDrop/Amp High
4 AWG21.15 mm²85 A96.15 V (20.03%)383.8 V158.6 V (33.04%)149883.8 WDrop/Amp High
3 AWG26.67 mm²100 A76.25 V (15.89%)403.8 V125.78 V (26.2%)118861.7 WDrop/Amp High
2 AWG33.62 mm²115 A60.49 V (12.6%)419.5 V99.78 V (20.79%)94290.4 WDrop/Amp High
1 AWG42.41 mm²130 A47.95 V (9.99%)432.0 V79.1 V (16.48%)74747.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A38.02 V (7.92%)442.0 V62.71 V (13.06%)59264.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A30.16 V (6.28%)449.8 V49.75 V (10.36%)47012.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A23.92 V (4.98%)456.1 V39.46 V (8.22%)37290.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A18.97 V (3.95%)461.0 V31.29 V (6.52%)29571.3 WDrop/Amp High
250 kcmil126.7 mm²255 A16.05 V (3.34%)463.9 V26.48 V (5.52%)25020.1 WDrop/Amp High
300 kcmil152.0 mm²285 A13.38 V (2.79%)466.6 V22.07 V (4.6%)20855.5 WDrop/Amp High
350 kcmil177.3 mm²310 A11.47 V (2.39%)468.5 V18.92 V (3.94%)17879.5 WDrop/Amp High
400 kcmil202.7 mm²335 A10.03 V (2.09%)470.0 V16.55 V (3.45%)15639.1 WDrop/Amp High
500 kcmil253.4 mm²380 A8.03 V (1.67%)472.0 V13.24 V (2.76%)12510.0 WDrop/Amp High
600 kcmil304.0 mm²420 A6.69 V (1.39%)473.3 V11.03 V (2.3%)10427.8 WDrop/Amp High
750 kcmil380.0 mm²475 A5.35 V (1.11%)474.6 V8.83 V (1.84%)8342.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.01 V (0.84%)476.0 V6.62 V (1.38%)6256.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 200 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 200 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.0V (0.42%) and delivers 478.0V at the load.

What size aluminum wire is required for 900 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.62V (1.38%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.