325 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 10.54V (2.54%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 17.39V (4.19%)
Voltage at Load404.5 VLine Loss: 5933.5 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2810.83 V (677.31%)0.0 V4636.56 V (1117.24%)1582262.5 WDrop High
2.5 mm²24 A18 A1686.5 V (406.39%)0.0 V2781.93 V (670.35%)949357.5 WDrop High
4 mm²32 A25 A1054.06 V (253.99%)0.0 V1738.71 V (418.97%)593348.4 WDrop High
6 mm²41 A32 A702.71 V (169.33%)0.0 V1159.14 V (279.31%)395565.6 WDrop High
10 mm²57 A44 A421.62 V (101.6%)0.0 V695.48 V (167.59%)237339.4 WDrop High
16 mm²76 A59 A263.52 V (63.5%)151.5 V434.68 V (104.74%)148337.1 WDrop High
25 mm²101 A78 A168.65 V (40.64%)246.4 V278.19 V (67.03%)94935.8 WDrop High
35 mm²125 A97 A120.46 V (29.03%)294.5 V198.71 V (47.88%)67811.2 WDrop High
50 mm²151 A118 A84.32 V (20.32%)330.7 V139.1 V (33.52%)47467.9 WDrop High
70 mm²192 A150 A60.23 V (14.51%)354.8 V99.35 V (23.94%)33905.6 WDrop High
95 mm²232 A181 A44.38 V (10.69%)370.6 V73.21 V (17.64%)24983.1 WDrop High
120 mm²269 A210 A35.14 V (8.47%)379.9 V57.96 V (13.97%)19778.3 WDrop High
150 mm²309 A241 A28.11 V (6.77%)386.9 V46.37 V (11.17%)15822.6 WDrop High
185 mm²353 A275 A22.79 V (5.49%)392.2 V37.59 V (9.06%)12829.2 WDrop High
240 mm²415 A324 A17.57 V (4.23%)397.4 V28.98 V (6.98%)9889.1 W~ ≤5%
300 mm²477 A372 A14.05 V (3.39%)400.9 V23.18 V (5.59%)7911.3 W~ ≤5%
400 mm²570 A445 A10.54 V (2.54%)404.5 V17.39 V (4.19%)5933.5 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 325A over 350m at 415V (voltage drop: 10.54V or 2.54%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.