425 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 425 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)3× 400 mm²Drop: 1.21V (2.53%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 6.0V (12.5%)
Voltage at Load46.8 VLine Loss: 515.4 W
Max Power & Breaker20.4 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A970.13 V (2021.11%)0.0 V1600.27 V (3333.89%)412306.7 WDrop High
2.5 mm²24 A18 A582.08 V (1212.67%)0.0 V960.16 V (2000.33%)247384.0 WDrop High
4 mm²32 A25 A363.8 V (757.92%)0.0 V600.1 V (1250.21%)154615.0 WDrop High
6 mm²41 A32 A242.53 V (505.28%)0.0 V400.07 V (833.47%)103076.7 WDrop High
10 mm²57 A44 A145.52 V (303.17%)0.0 V240.04 V (500.08%)61846.0 WDrop High
16 mm²76 A59 A90.95 V (189.48%)0.0 V150.03 V (312.55%)38653.8 WDrop High
25 mm²101 A78 A58.21 V (121.27%)0.0 V96.02 V (200.03%)24738.4 WDrop High
35 mm²125 A97 A41.58 V (86.62%)6.4 V68.58 V (142.88%)17670.3 WDrop High
50 mm²151 A118 A29.1 V (60.63%)18.9 V48.01 V (100.02%)12369.2 WDrop High
70 mm²192 A150 A20.79 V (43.31%)27.2 V34.29 V (71.44%)8835.1 WDrop High
95 mm²232 A181 A15.32 V (31.91%)32.7 V25.27 V (52.64%)6510.1 WDrop High
120 mm²269 A210 A12.13 V (25.26%)35.9 V20.0 V (41.67%)5153.8 WDrop High
150 mm²309 A241 A9.7 V (20.21%)38.3 V16.0 V (33.34%)4123.1 WDrop High
185 mm²353 A275 A7.87 V (16.39%)40.1 V12.98 V (27.03%)3343.0 WDrop High
240 mm²415 A324 A6.06 V (12.63%)41.9 V10.0 V (20.84%)2576.9 WDrop High
300 mm²477 A372 A4.85 V (10.11%)43.1 V8.0 V (16.67%)2061.5 WDrop High
400 mm²570 A445 A3.64 V (7.58%)44.4 V6.0 V (12.5%)1546.2 WDrop High

FAQ — 425 Amp Cable Size at 80 Meters (48V DC (LiFePO4 Battery Bank / Telecom))

What mm² cable size is required for 425A at 80 meters (48V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 3× 400 mm² copper cable for 425A over 80m at 48V (voltage drop: 1.21V or 2.53%).

What is the power capacity of 425A at 48V?

At unity power factor, 425A at 48V supports 20.4 kW with a standard 450A circuit breaker.