550 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 550 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)2× 400 mm²Drop: 8.92V (2.15%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 29.42V (7.09%)
Voltage at Load406.1 VLine Loss: 8496.5 W
Max Power & Breaker395.34 kW600A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 550A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A4756.79 V (1146.21%)0.0 V7846.48 V (1890.72%)4531450.0 WDrop High
2.5 mm²24 A18 A2854.07 V (687.73%)0.0 V4707.89 V (1134.43%)2718870.0 WDrop High
4 mm²32 A25 A1783.8 V (429.83%)0.0 V2942.43 V (709.02%)1699293.7 WDrop High
6 mm²41 A32 A1189.2 V (286.55%)0.0 V1961.62 V (472.68%)1132862.5 WDrop High
10 mm²57 A44 A713.52 V (171.93%)0.0 V1176.97 V (283.61%)679717.5 WDrop High
16 mm²76 A59 A445.95 V (107.46%)0.0 V735.61 V (177.25%)424823.4 WDrop High
25 mm²101 A78 A285.41 V (68.77%)129.6 V470.79 V (113.44%)271887.0 WDrop High
35 mm²125 A97 A203.86 V (49.12%)211.1 V336.28 V (81.03%)194205.0 WDrop High
50 mm²151 A118 A142.7 V (34.39%)272.3 V235.39 V (56.72%)135943.5 WDrop High
70 mm²192 A150 A101.93 V (24.56%)313.1 V168.14 V (40.52%)97102.5 WDrop High
95 mm²232 A181 A75.11 V (18.1%)339.9 V123.89 V (29.85%)71549.2 WDrop High
120 mm²269 A210 A59.46 V (14.33%)355.5 V98.08 V (23.63%)56643.1 WDrop High
150 mm²309 A241 A47.57 V (11.46%)367.4 V78.46 V (18.91%)45314.5 WDrop High
185 mm²353 A275 A38.57 V (9.29%)376.4 V63.62 V (15.33%)36741.5 WDrop High
240 mm²415 A324 A29.73 V (7.16%)385.3 V49.04 V (11.82%)28321.6 WDrop High
300 mm²477 A372 A23.78 V (5.73%)391.2 V39.23 V (9.45%)22657.2 WDrop High
400 mm²570 A445 A17.84 V (4.3%)397.2 V29.42 V (7.09%)16992.9 W~ ≤5%

FAQ — 550 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 550A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 2× 400 mm² copper cable for 550A over 350m at 415V (voltage drop: 8.92V or 2.15%).

What is the power capacity of 550A at 415V?

At unity power factor, 550A at 415V supports 395.34 kW with a standard 600A circuit breaker.