⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabeltværsnit for 110 Ampere ved 600 Meter (230V)

Beregning af kabeltværsnit (mm²), spændingsfald og sikringsstørrelse efter dansk standard DS/HD 60364 for 110 A over 600 m ved 230V.

Copper Cable (≤3% Drop)2× 400 mm²Drop: 3.53V (1.53%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.65V (5.06%)
Voltage at Load226.5 VLine Loss: 388.4 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 600m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1883.2 V (818.78%)0.0 V3106.4 V (1350.61%)207152.0 WDrop High
2.5 mm²24 A18 A1129.92 V (491.27%)0.0 V1863.84 V (810.37%)124291.2 WDrop High
4 mm²32 A25 A706.2 V (307.04%)0.0 V1164.9 V (506.48%)77682.0 WDrop High
6 mm²41 A32 A470.8 V (204.7%)0.0 V776.6 V (337.65%)51788.0 WDrop High
10 mm²57 A44 A282.48 V (122.82%)0.0 V465.96 V (202.59%)31072.8 WDrop High
16 mm²76 A59 A176.55 V (76.76%)53.4 V291.23 V (126.62%)19420.5 WDrop High
25 mm²101 A78 A112.99 V (49.13%)117.0 V186.38 V (81.04%)12429.1 WDrop High
35 mm²125 A97 A80.71 V (35.09%)149.3 V133.13 V (57.88%)8877.9 WDrop High
50 mm²151 A118 A56.5 V (24.56%)173.5 V93.19 V (40.52%)6214.6 WDrop High
70 mm²192 A150 A40.35 V (17.55%)189.6 V66.57 V (28.94%)4439.0 WDrop High
95 mm²232 A181 A29.73 V (12.93%)200.3 V49.05 V (21.33%)3270.8 WDrop High
120 mm²269 A210 A23.54 V (10.23%)206.5 V38.83 V (16.88%)2589.4 WDrop High
150 mm²309 A241 A18.83 V (8.19%)211.2 V31.06 V (13.51%)2071.5 WDrop High
185 mm²353 A275 A15.27 V (6.64%)214.7 V25.19 V (10.95%)1679.6 WDrop High
240 mm²415 A324 A11.77 V (5.12%)218.2 V19.41 V (8.44%)1294.7 WDrop High
300 mm²477 A372 A9.42 V (4.09%)220.6 V15.53 V (6.75%)1035.8 W~ ≤5%
400 mm²570 A445 A7.06 V (3.07%)222.9 V11.65 V (5.06%)776.8 W~ ≤5%

FAQ — Kabeltværsnit for 110 Ampere ved 600 Meter (230V)

Hvilket kabeltværsnit kræves til 110A ved 600 meter (230V)?

Til 110 Ampere over 600 meter ved 230V anbefales 2× 400 mm² kobberkabel (spændingsfald 3.53V / 1.53%).

Hvor mange kW svarer 110A ved 230V til?

Det svarer til 25.3 kW med en anbefalet sikring på 110A.