⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

Kabelarea för 110 Ampere vid 90 Meter (230V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 110 A över 90 m vid 230V.

Copper Cable (≤3% Drop)70 mm²Drop: 6.05V (2.63%)
Aluminum Cable (≤3% Drop)120 mm²Drop: 5.82V (2.53%)
Voltage at Load223.9 VLine Loss: 665.8 W
Max Power & Breaker25.3 kW110A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 110A at 90m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A282.48 V (122.82%)0.0 V465.96 V (202.59%)31072.8 WDrop High
2.5 mm²24 A18 A169.49 V (73.69%)60.5 V279.58 V (121.55%)18643.7 WDrop High
4 mm²32 A25 A105.93 V (46.06%)124.1 V174.73 V (75.97%)11652.3 WDrop High
6 mm²41 A32 A70.62 V (30.7%)159.4 V116.49 V (50.65%)7768.2 WDrop High
10 mm²57 A44 A42.37 V (18.42%)187.6 V69.89 V (30.39%)4660.9 WDrop High
16 mm²76 A59 A26.48 V (11.51%)203.5 V43.68 V (18.99%)2913.1 WDrop High
25 mm²101 A78 A16.95 V (7.37%)213.1 V27.96 V (12.16%)1864.4 WDrop High
35 mm²125 A97 A12.11 V (5.26%)217.9 V19.97 V (8.68%)1331.7 WDrop High
50 mm²151 A118 A8.47 V (3.68%)221.5 V13.98 V (6.08%)932.2 W~ ≤5%
70 mm²192 A150 A6.05 V (2.63%)223.9 V9.98 V (4.34%)665.8 W✓ OK (≤3%)
95 mm²232 A181 A4.46 V (1.94%)225.5 V7.36 V (3.2%)490.6 W✓ OK (≤3%)
120 mm²269 A210 A3.53 V (1.54%)226.5 V5.82 V (2.53%)388.4 W✓ OK (≤3%)
150 mm²309 A241 A2.82 V (1.23%)227.2 V4.66 V (2.03%)310.7 W✓ OK (≤3%)
185 mm²353 A275 A2.29 V (1.0%)227.7 V3.78 V (1.64%)251.9 W✓ OK (≤3%)
240 mm²415 A324 A1.77 V (0.77%)228.2 V2.91 V (1.27%)194.2 W✓ OK (≤3%)
300 mm²477 A372 A1.41 V (0.61%)228.6 V2.33 V (1.01%)155.4 W✓ OK (≤3%)
400 mm²570 A445 A1.06 V (0.46%)228.9 V1.75 V (0.76%)116.5 W✓ OK (≤3%)

FAQ — Kabelarea för 110 Ampere vid 90 Meter (230V)

Vilken kabelarea krävs för 110A vid 90 meter (230V)?

För 110 Ampere över 90 meter vid 230V rekommenderas 70 mm² kopparkabel för att hålla spänningsfallet under 3% (6.05V / 2.63%).

Hur stor effekt motsvarar 110A vid 230V?

Det motsvarar 25.3 kW med en rekommenderad säkring på 110A.