Kabelarea för 425 Ampere vid 175 Meter (400V)

Komplett dimensionering av kabelarea (mm²), spänningsfall och säkring enligt svensk elstandard (SS 436 40 00 / IEC 60364) för 425 A över 175 m vid 400V.

Copper Cable (≤3% Drop)300 mm²Drop: 9.19V (2.3%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 11.37V (2.84%)
Voltage at Load390.8 VLine Loss: 6764.4 W
Max Power & Breaker294.45 kW450A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 425A at 175m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A1837.85 V (459.46%)0.0 V3031.59 V (757.9%)1352881.2 WDrop High
2.5 mm²24 A18 A1102.71 V (275.68%)0.0 V1818.96 V (454.74%)811728.7 WDrop High
4 mm²32 A25 A689.19 V (172.3%)0.0 V1136.85 V (284.21%)507330.5 WDrop High
6 mm²41 A32 A459.46 V (114.87%)0.0 V757.9 V (189.47%)338220.3 WDrop High
10 mm²57 A44 A275.68 V (68.92%)124.3 V454.74 V (113.68%)202932.2 WDrop High
16 mm²76 A59 A172.3 V (43.07%)227.7 V284.21 V (71.05%)126832.6 WDrop High
25 mm²101 A78 A110.27 V (27.57%)289.7 V181.9 V (45.47%)81172.9 WDrop High
35 mm²125 A97 A78.77 V (19.69%)321.2 V129.93 V (32.48%)57980.6 WDrop High
50 mm²151 A118 A55.14 V (13.78%)344.9 V90.95 V (22.74%)40586.4 WDrop High
70 mm²192 A150 A39.38 V (9.85%)360.6 V64.96 V (16.24%)28990.3 WDrop High
95 mm²232 A181 A29.02 V (7.25%)371.0 V47.87 V (11.97%)21361.3 WDrop High
120 mm²269 A210 A22.97 V (5.74%)377.0 V37.89 V (9.47%)16911.0 WDrop High
150 mm²309 A241 A18.38 V (4.59%)381.6 V30.32 V (7.58%)13528.8 WDrop High
185 mm²353 A275 A14.9 V (3.73%)385.1 V24.58 V (6.15%)10969.3 WDrop High
240 mm²415 A324 A11.49 V (2.87%)388.5 V18.95 V (4.74%)8455.5 WDrop High
300 mm²477 A372 A9.19 V (2.3%)390.8 V15.16 V (3.79%)6764.4 W✓ OK (≤3%)
400 mm²570 A445 A6.89 V (1.72%)393.1 V11.37 V (2.84%)5073.3 W✓ OK (≤3%)

FAQ — Kabelarea för 425 Ampere vid 175 Meter (400V)

Vilken kabelarea krävs för 425A vid 175 meter (400V)?

För 425 Ampere över 175 meter vid 400V rekommenderas 300 mm² kopparkabel för att hålla spänningsfallet under 3% (9.19V / 2.3%).

Hur stor effekt motsvarar 425A vid 400V?

Det motsvarar 294.45 kW med en rekommenderad säkring på 450A.