🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 275 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 6.07V (2.53%)
Voltage at Load End234.1 VLoss: 5.85 V (643.8 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A189.72 V (79.05%)50.3 V312.95 V (130.4%)20869.6 WDrop/Amp High
12 AWG3.31 mm²20 A119.22 V (49.68%)120.8 V196.66 V (81.94%)13114.4 WDrop/Amp High
10 AWG5.26 mm²30 A75.02 V (31.26%)165.0 V123.75 V (51.56%)8252.6 WDrop/Amp High
8 AWG8.37 mm²50 A47.15 V (19.64%)192.9 V77.77 V (32.4%)5186.2 WDrop/Amp High
6 AWG13.3 mm²65 A29.67 V (12.36%)210.3 V48.94 V (20.39%)3263.8 WDrop/Amp High
4 AWG21.15 mm²85 A18.66 V (7.77%)221.3 V30.78 V (12.82%)2052.4 WDrop/Amp High
3 AWG26.67 mm²100 A14.8 V (6.17%)225.2 V24.41 V (10.17%)1627.6 WDrop/Amp High
2 AWG33.62 mm²115 A11.74 V (4.89%)228.3 V19.36 V (8.07%)1291.2 W~ ≤5%
1 AWG42.41 mm²130 A9.3 V (3.88%)230.7 V15.35 V (6.4%)1023.5 W~ ≤5%
1/0 AWG53.49 mm²150 A7.38 V (3.07%)232.6 V12.17 V (5.07%)811.5 W~ ≤5%
2/0 AWG67.43 mm²175 A5.85 V (2.44%)234.1 V9.65 V (4.02%)643.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.64 V (1.93%)235.4 V7.66 V (3.19%)510.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.68 V (1.53%)236.3 V6.07 V (2.53%)404.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.11 V (1.3%)236.9 V5.14 V (2.14%)342.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.6 V (1.08%)237.4 V4.28 V (1.78%)285.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.23 V (0.93%)237.8 V3.67 V (1.53%)244.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.95 V (0.81%)238.1 V3.21 V (1.34%)214.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.56 V (0.65%)238.4 V2.57 V (1.07%)171.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.3 V (0.54%)238.7 V2.14 V (0.89%)142.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.04 V (0.43%)239.0 V1.71 V (0.71%)114.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.78 V (0.32%)239.2 V1.28 V (0.54%)85.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 275 feet one-way at 240V (1-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.85V (2.44%) and delivers 234.1V at the load.

What size aluminum wire is required for 110 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 6.07V (2.53%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.