🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.12%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 10.54V (2.2%)
Voltage at Load End469.8 VLoss: 10.17 V (1936.7 W)
Power & Breaker (125%)91.45 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A164.31 V (34.23%)315.7 V271.03 V (56.46%)31304.4 WDrop/Amp High
12 AWG3.31 mm²20 A103.25 V (21.51%)376.8 V170.31 V (35.48%)19671.6 WDrop/Amp High
10 AWG5.26 mm²30 A64.97 V (13.54%)415.0 V107.17 V (22.33%)12378.9 WDrop/Amp High
8 AWG8.37 mm²50 A40.83 V (8.51%)439.2 V67.35 V (14.03%)7779.3 WDrop/Amp High
6 AWG13.3 mm²65 A25.7 V (5.35%)454.3 V42.39 V (8.83%)4895.7 WDrop/Amp High
4 AWG21.15 mm²85 A16.16 V (3.37%)463.8 V26.65 V (5.55%)3078.6 WDrop/Amp High
3 AWG26.67 mm²100 A12.81 V (2.67%)467.2 V21.14 V (4.4%)2441.4 WDrop/Amp High
2 AWG33.62 mm²115 A10.17 V (2.12%)469.8 V16.77 V (3.49%)1936.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A8.06 V (1.68%)471.9 V13.29 V (2.77%)1535.3 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A6.39 V (1.33%)473.6 V10.54 V (2.2%)1217.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A5.07 V (1.06%)474.9 V8.36 V (1.74%)965.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.02 V (0.84%)476.0 V6.63 V (1.38%)765.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.19 V (0.66%)476.8 V5.26 V (1.1%)607.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.7 V (0.56%)477.3 V4.45 V (0.93%)513.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.25 V (0.47%)477.8 V3.71 V (0.77%)428.4 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.93 V (0.4%)478.1 V3.18 V (0.66%)367.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.69 V (0.35%)478.3 V2.78 V (0.58%)321.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.35 V (0.28%)478.7 V2.22 V (0.46%)257.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.12 V (0.23%)478.9 V1.85 V (0.39%)214.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.9 V (0.19%)479.1 V1.48 V (0.31%)171.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.67 V (0.14%)479.3 V1.11 V (0.23%)128.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 275 feet one-way at 480V (3-Phase), you need 2 AWG copper wire. This produces a voltage drop of 10.17V (2.12%) and delivers 469.8V at the load.

What size aluminum wire is required for 110 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 10.54V (2.2%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.