🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 275 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)4/0 AWG107.2 mm² · Drop: 1.36%
Aluminum Wire (≤3% Drop)300 kcmilDrop: 7.59V (1.58%)
Voltage at Load End473.5 VLoss: 6.52 V (2541.3 W)
Power & Breaker (125%)187.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 275 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A336.08 V (70.02%)143.9 V554.37 V (115.49%)130973.8 WDrop/Amp High
12 AWG3.31 mm²20 A211.19 V (44.0%)268.8 V348.37 V (72.58%)82303.8 WDrop/Amp High
10 AWG5.26 mm²30 A132.9 V (27.69%)347.1 V219.22 V (45.67%)51791.9 WDrop/Amp High
8 AWG8.37 mm²50 A83.52 V (17.4%)396.5 V137.77 V (28.7%)32547.8 WDrop/Amp High
6 AWG13.3 mm²65 A52.56 V (10.95%)427.4 V86.7 V (18.06%)20483.1 WDrop/Amp High
4 AWG21.15 mm²85 A33.05 V (6.89%)446.9 V54.52 V (11.36%)12880.6 WDrop/Amp High
3 AWG26.67 mm²100 A26.21 V (5.46%)453.8 V43.24 V (9.01%)10214.7 WDrop/Amp High
2 AWG33.62 mm²115 A20.79 V (4.33%)459.2 V34.3 V (7.15%)8103.1 WDrop/Amp High
1 AWG42.41 mm²130 A16.48 V (3.43%)463.5 V27.19 V (5.66%)6423.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.07 V (2.72%)466.9 V21.56 V (4.49%)5093.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.37 V (2.16%)469.6 V17.1 V (3.56%)4040.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.22 V (1.71%)471.8 V13.56 V (2.83%)3204.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.52 V (1.36%)473.5 V10.76 V (2.24%)2541.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A5.52 V (1.15%)474.5 V9.1 V (1.9%)2150.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A4.6 V (0.96%)475.4 V7.59 V (1.58%)1792.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A3.94 V (0.82%)476.1 V6.5 V (1.35%)1536.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.45 V (0.72%)476.6 V5.69 V (1.19%)1344.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A2.76 V (0.57%)477.2 V4.55 V (0.95%)1075.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.3 V (0.48%)477.7 V3.79 V (0.79%)896.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.84 V (0.38%)478.2 V3.03 V (0.63%)716.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.38 V (0.29%)478.6 V2.28 V (0.47%)537.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 275 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 275 feet one-way at 480V (3-Phase), you need 4/0 AWG copper wire. This produces a voltage drop of 6.52V (1.36%) and delivers 473.5V at the load.

What size aluminum wire is required for 225 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 300 kcmil to maintain voltage drop at 7.59V (1.58%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.