⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-25)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

225 Amp Wire Size at 300 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 225 A load over a 300 ft (91.4 m) one-way run.

Copper Wire (≤3% Drop)250 kcmil126.7 mm² · Drop: 2.89%
Aluminum Wire (≤3% Drop)400 kcmilDrop: 6.21V (2.98%)
Voltage at Load End202.0 VLoss: 6.02 V (2345.6 W)
Power & Breaker (125%)81.06 kW300A Breaker Recommended

All AWG & kcmil Wire Gauges for 225 Amps at 300 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A366.63 V (176.27%)0.0 V604.77 V (290.76%)142880.5 WDrop/Amp High
12 AWG3.31 mm²20 A230.39 V (110.76%)0.0 V380.04 V (182.71%)89785.9 WDrop/Amp High
10 AWG5.26 mm²30 A144.98 V (69.7%)63.0 V239.15 V (114.98%)56500.3 WDrop/Amp High
8 AWG8.37 mm²50 A91.11 V (43.8%)116.9 V150.29 V (72.25%)35506.7 WDrop/Amp High
6 AWG13.3 mm²65 A57.34 V (27.57%)150.7 V94.58 V (45.47%)22345.2 WDrop/Amp High
4 AWG21.15 mm²85 A36.06 V (17.33%)171.9 V59.48 V (28.59%)14051.6 WDrop/Amp High
3 AWG26.67 mm²100 A28.59 V (13.75%)179.4 V47.17 V (22.68%)11143.3 WDrop/Amp High
2 AWG33.62 mm²115 A22.68 V (10.91%)185.3 V37.42 V (17.99%)8839.7 WDrop/Amp High
1 AWG42.41 mm²130 A17.98 V (8.64%)190.0 V29.66 V (14.26%)7007.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.26 V (6.85%)193.7 V23.52 V (11.31%)5556.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.31 V (5.44%)196.7 V18.66 V (8.97%)4407.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.97 V (4.31%)199.0 V14.8 V (7.11%)3496.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.11 V (3.42%)200.9 V11.73 V (5.64%)2772.3 W~ ≤5%
250 kcmil126.7 mm²255 A6.02 V (2.89%)202.0 V9.93 V (4.77%)2345.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A5.02 V (2.41%)203.0 V8.28 V (3.98%)1955.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A4.3 V (2.07%)203.7 V7.09 V (3.41%)1676.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A3.76 V (1.81%)204.2 V6.21 V (2.98%)1466.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.01 V (1.45%)205.0 V4.96 V (2.39%)1172.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.51 V (1.21%)205.5 V4.14 V (1.99%)977.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.01 V (0.96%)206.0 V3.31 V (1.59%)782.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.51 V (0.72%)206.5 V2.48 V (1.19%)586.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 225 amps at 300 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 225A load over 300 feet one-way at 208V (3-Phase), you need 250 kcmil copper wire. This produces a voltage drop of 6.02V (2.89%) and delivers 202.0V at the load.

What size aluminum wire is required for 225 amps at 300 feet?

Using aluminum conductors (75°C rating), you should use 400 kcmil to maintain voltage drop at 6.21V (2.98%).

What breaker size is needed for a 225A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (225A × 1.25 = 281.2A), which corresponds to a standard 300A circuit breaker.