🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 200 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.74%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 4.6V (1.92%)
Voltage at Load End235.8 VLoss: 4.18 V (1359.6 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A407.67 V (169.86%)0.0 V672.47 V (280.19%)132492.8 WDrop/Amp High
12 AWG3.31 mm²20 A256.18 V (106.74%)0.0 V422.58 V (176.07%)83258.3 WDrop/Amp High
10 AWG5.26 mm²30 A161.21 V (67.17%)78.8 V265.92 V (110.8%)52392.6 WDrop/Amp High
8 AWG8.37 mm²50 A101.31 V (42.21%)138.7 V167.11 V (69.63%)32925.3 WDrop/Amp High
6 AWG13.3 mm²65 A63.76 V (26.56%)176.2 V105.17 V (43.82%)20720.7 WDrop/Amp High
4 AWG21.15 mm²85 A40.09 V (16.71%)199.9 V66.13 V (27.56%)13030.0 WDrop/Amp High
3 AWG26.67 mm²100 A31.79 V (13.25%)208.2 V52.45 V (21.85%)10333.1 WDrop/Amp High
2 AWG33.62 mm²115 A25.22 V (10.51%)214.8 V41.6 V (17.34%)8197.1 WDrop/Amp High
1 AWG42.41 mm²130 A19.99 V (8.33%)220.0 V32.98 V (13.74%)6498.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.85 V (6.61%)224.1 V26.15 V (10.9%)5152.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.58 V (5.24%)227.4 V20.74 V (8.64%)4087.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.97 V (4.16%)230.0 V16.45 V (6.86%)3241.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.91 V (3.3%)232.1 V13.05 V (5.44%)2570.8 WDrop/Amp High
250 kcmil126.7 mm²255 A6.69 V (2.79%)233.3 V11.04 V (4.6%)2175.1 WDrop/Amp High
300 kcmil152.0 mm²285 A5.58 V (2.32%)234.4 V9.2 V (3.83%)1813.1 WDrop/Amp High
350 kcmil177.3 mm²310 A4.78 V (1.99%)235.2 V7.89 V (3.29%)1554.3 WDrop/Amp High
400 kcmil202.7 mm²335 A4.18 V (1.74%)235.8 V6.9 V (2.88%)1359.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.35 V (1.39%)236.7 V5.52 V (2.3%)1087.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.79 V (1.16%)237.2 V4.6 V (1.92%)906.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.23 V (0.93%)237.8 V3.68 V (1.53%)725.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.67 V (0.7%)238.3 V2.76 V (1.15%)543.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 200 feet one-way at 240V (1-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 4.18V (1.74%) and delivers 235.8V at the load.

What size aluminum wire is required for 325 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 4.6V (1.92%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.