🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 225 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)400 kcmil202.7 mm² · Drop: 1.7%
Aluminum Wire (≤3% Drop)600 kcmilDrop: 4.48V (1.87%)
Voltage at Load End235.9 VLoss: 4.08 V (2294.3 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 225 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A397.18 V (165.49%)0.0 V655.17 V (272.99%)223581.5 WDrop/Amp High
12 AWG3.31 mm²20 A249.59 V (104.0%)0.0 V411.71 V (171.54%)140498.4 WDrop/Amp High
10 AWG5.26 mm²30 A157.06 V (65.44%)82.9 V259.08 V (107.95%)88412.5 WDrop/Amp High
8 AWG8.37 mm²50 A98.7 V (41.13%)141.3 V162.81 V (67.84%)55561.5 WDrop/Amp High
6 AWG13.3 mm²65 A62.12 V (25.88%)177.9 V102.46 V (42.69%)34966.1 WDrop/Amp High
4 AWG21.15 mm²85 A39.06 V (16.28%)200.9 V64.43 V (26.85%)21988.2 WDrop/Amp High
3 AWG26.67 mm²100 A30.98 V (12.91%)209.0 V51.1 V (21.29%)17437.2 WDrop/Amp High
2 AWG33.62 mm²115 A24.57 V (10.24%)215.4 V40.53 V (16.89%)13832.5 WDrop/Amp High
1 AWG42.41 mm²130 A19.48 V (8.12%)220.5 V32.13 V (13.39%)10965.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A15.44 V (6.44%)224.6 V25.48 V (10.62%)8694.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A12.25 V (5.1%)227.7 V20.21 V (8.42%)6896.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.72 V (4.05%)230.3 V16.03 V (6.68%)5470.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.71 V (3.21%)232.3 V12.71 V (5.3%)4338.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.52 V (2.72%)233.5 V10.76 V (4.48%)3670.5 WDrop/Amp High
300 kcmil152.0 mm²285 A5.44 V (2.26%)234.6 V8.97 V (3.74%)3059.5 WDrop/Amp High
350 kcmil177.3 mm²310 A4.66 V (1.94%)235.3 V7.69 V (3.2%)2623.0 WDrop/Amp High
400 kcmil202.7 mm²335 A4.08 V (1.7%)235.9 V6.72 V (2.8%)2294.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A3.26 V (1.36%)236.7 V5.38 V (2.24%)1835.2 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A2.72 V (1.13%)237.3 V4.48 V (1.87%)1529.8 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A2.17 V (0.91%)237.8 V3.59 V (1.49%)1223.8 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.63 V (0.68%)238.4 V2.69 V (1.12%)917.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 225 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 225 feet one-way at 240V (3-Phase), you need 400 kcmil copper wire. This produces a voltage drop of 4.08V (1.7%) and delivers 235.9V at the load.

What size aluminum wire is required for 325 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 600 kcmil to maintain voltage drop at 4.48V (1.87%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.