🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.72%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 7.17V (2.99%)
Voltage at Load End233.5 VLoss: 6.52 V (3670.5 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A794.37 V (330.99%)0.0 V1310.34 V (545.97%)447163.0 WDrop/Amp High
12 AWG3.31 mm²20 A499.18 V (207.99%)0.0 V823.41 V (343.09%)280996.7 WDrop/Amp High
10 AWG5.26 mm²30 A314.12 V (130.88%)0.0 V518.16 V (215.9%)176824.9 WDrop/Amp High
8 AWG8.37 mm²50 A197.41 V (82.25%)42.6 V325.63 V (135.68%)111123.0 WDrop/Amp High
6 AWG13.3 mm²65 A124.23 V (51.76%)115.8 V204.92 V (85.39%)69932.3 WDrop/Amp High
4 AWG21.15 mm²85 A78.12 V (32.55%)161.9 V128.87 V (53.69%)43976.3 WDrop/Amp High
3 AWG26.67 mm²100 A61.95 V (25.81%)178.0 V102.19 V (42.58%)34874.4 WDrop/Amp High
2 AWG33.62 mm²115 A49.15 V (20.48%)190.9 V81.07 V (33.78%)27665.1 WDrop/Amp High
1 AWG42.41 mm²130 A38.96 V (16.23%)201.0 V64.27 V (26.78%)21931.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A30.89 V (12.87%)209.1 V50.95 V (21.23%)17388.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A24.5 V (10.21%)215.5 V40.42 V (16.84%)13793.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A19.44 V (8.1%)220.6 V32.06 V (13.36%)10941.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A15.41 V (6.42%)224.6 V25.42 V (10.59%)8676.3 WDrop/Amp High
250 kcmil126.7 mm²255 A13.04 V (5.43%)227.0 V21.51 V (8.96%)7341.0 WDrop/Amp High
300 kcmil152.0 mm²285 A10.87 V (4.53%)229.1 V17.93 V (7.47%)6119.1 WDrop/Amp High
350 kcmil177.3 mm²310 A9.32 V (3.88%)230.7 V15.37 V (6.41%)5245.9 WDrop/Amp High
400 kcmil202.7 mm²335 A8.15 V (3.4%)231.8 V13.45 V (5.6%)4588.6 W~ ≤5%
500 kcmil253.4 mm²380 A6.52 V (2.72%)233.5 V10.76 V (4.48%)3670.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A5.44 V (2.26%)234.6 V8.97 V (3.74%)3059.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A4.35 V (1.81%)235.7 V7.17 V (2.99%)2447.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A3.26 V (1.36%)236.7 V5.38 V (2.24%)1835.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 450 feet one-way at 240V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 6.52V (2.72%) and delivers 233.5V at the load.

What size aluminum wire is required for 325 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 7.17V (2.99%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.