🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 500 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.75%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 6.9V (5.75%)
Voltage at Load End117.9 VLoss: 2.09 V (679.9 W)
Power & Breaker (125%)39.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 500 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1019.17 V (849.31%)0.0 V1681.16 V (1400.97%)331231.9 WDrop/Amp High
12 AWG3.31 mm²20 A640.45 V (533.71%)0.0 V1056.44 V (880.37%)208145.7 WDrop/Amp High
10 AWG5.26 mm²30 A403.02 V (335.85%)0.0 V664.79 V (554.0%)130981.4 WDrop/Amp High
8 AWG8.37 mm²50 A253.27 V (211.06%)0.0 V417.78 V (348.15%)82313.3 WDrop/Amp High
6 AWG13.3 mm²65 A159.39 V (132.82%)0.0 V262.92 V (219.1%)51801.7 WDrop/Amp High
4 AWG21.15 mm²85 A100.23 V (83.53%)19.8 V165.33 V (137.78%)32575.0 WDrop/Amp High
3 AWG26.67 mm²100 A79.49 V (66.24%)40.5 V131.11 V (109.26%)25832.9 WDrop/Amp High
2 AWG33.62 mm²115 A63.05 V (52.55%)56.9 V104.01 V (86.68%)20492.6 WDrop/Amp High
1 AWG42.41 mm²130 A49.99 V (41.65%)70.0 V82.45 V (68.71%)16245.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A39.63 V (33.03%)80.4 V65.37 V (54.48%)12880.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.44 V (26.2%)88.6 V51.86 V (43.22%)10217.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A24.94 V (20.78%)95.1 V41.13 V (34.28%)8104.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A19.78 V (16.48%)100.2 V32.62 V (27.18%)6426.9 WDrop/Amp High
250 kcmil126.7 mm²255 A16.73 V (13.94%)103.3 V27.6 V (23.0%)5437.7 WDrop/Amp High
300 kcmil152.0 mm²285 A13.95 V (11.62%)106.1 V23.01 V (19.17%)4532.6 WDrop/Amp High
350 kcmil177.3 mm²310 A11.96 V (9.96%)108.0 V19.72 V (16.44%)3885.9 WDrop/Amp High
400 kcmil202.7 mm²335 A10.46 V (8.72%)109.5 V17.25 V (14.38%)3398.9 WDrop/Amp High
500 kcmil253.4 mm²380 A8.37 V (6.97%)111.6 V13.8 V (11.5%)2718.9 WDrop/Amp High
600 kcmil304.0 mm²420 A6.97 V (5.81%)113.0 V11.5 V (9.59%)2266.3 WDrop/Amp High
750 kcmil380.0 mm²475 A5.58 V (4.65%)114.4 V9.2 V (7.67%)1813.1 W~ ≤5%
1000 kcmil506.7 mm²545 A4.18 V (3.49%)115.8 V6.9 V (5.75%)1359.7 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 500 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 500 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.09V (1.75%) and delivers 117.9V at the load.

What size aluminum wire is required for 325 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 6.9V (5.75%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.