🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.28V (3.45%)
Voltage at Load End233.3 VLoss: 6.69 V (2175.7 W)
Power & Breaker (125%)78.0 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1223.01 V (509.59%)0.0 V2017.39 V (840.58%)397478.2 WDrop/Amp High
12 AWG3.31 mm²20 A768.54 V (320.22%)0.0 V1267.73 V (528.22%)249774.9 WDrop/Amp High
10 AWG5.26 mm²30 A483.62 V (201.51%)0.0 V797.75 V (332.4%)157177.7 WDrop/Amp High
8 AWG8.37 mm²50 A303.93 V (126.64%)0.0 V501.34 V (208.89%)98776.0 WDrop/Amp High
6 AWG13.3 mm²65 A191.27 V (79.69%)48.7 V315.5 V (131.46%)62162.0 WDrop/Amp High
4 AWG21.15 mm²85 A120.28 V (50.12%)119.7 V198.4 V (82.67%)39090.1 WDrop/Amp High
3 AWG26.67 mm²100 A95.38 V (39.74%)144.6 V157.34 V (65.56%)30999.4 WDrop/Amp High
2 AWG33.62 mm²115 A75.67 V (31.53%)164.3 V124.81 V (52.01%)24591.2 WDrop/Amp High
1 AWG42.41 mm²130 A59.98 V (24.99%)180.0 V98.94 V (41.23%)19494.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A47.56 V (19.82%)192.4 V78.45 V (32.69%)15456.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A37.73 V (15.72%)202.3 V62.23 V (25.93%)12260.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A29.92 V (12.47%)210.1 V49.36 V (20.57%)9725.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.73 V (9.89%)216.3 V39.14 V (16.31%)7712.3 WDrop/Amp High
250 kcmil126.7 mm²255 A20.08 V (8.37%)219.9 V33.12 V (13.8%)6525.3 WDrop/Amp High
300 kcmil152.0 mm²285 A16.74 V (6.97%)223.3 V27.61 V (11.5%)5439.2 WDrop/Amp High
350 kcmil177.3 mm²310 A14.35 V (5.98%)225.7 V23.67 V (9.86%)4663.0 WDrop/Amp High
400 kcmil202.7 mm²335 A12.55 V (5.23%)227.5 V20.7 V (8.63%)4078.7 WDrop/Amp High
500 kcmil253.4 mm²380 A10.04 V (4.18%)230.0 V16.56 V (6.9%)3262.6 W~ ≤5%
600 kcmil304.0 mm²420 A8.37 V (3.49%)231.6 V13.8 V (5.75%)2719.6 W~ ≤5%
750 kcmil380.0 mm²475 A6.69 V (2.79%)233.3 V11.04 V (4.6%)2175.7 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A5.02 V (2.09%)235.0 V8.28 V (3.45%)1631.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 600 feet one-way at 240V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 6.69V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 325 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.28V (3.45%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.