🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.17V (2.99%)
Voltage at Load End234.2 VLoss: 5.8 V (3263.5 W)
Power & Breaker (125%)135.1 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1059.16 V (441.32%)0.0 V1747.12 V (727.96%)596217.4 WDrop/Amp High
12 AWG3.31 mm²20 A665.57 V (277.32%)0.0 V1097.89 V (457.45%)374662.3 WDrop/Amp High
10 AWG5.26 mm²30 A418.83 V (174.51%)0.0 V690.87 V (287.86%)235766.6 WDrop/Amp High
8 AWG8.37 mm²50 A263.21 V (109.67%)0.0 V434.17 V (180.9%)148163.9 WDrop/Amp High
6 AWG13.3 mm²65 A165.64 V (69.02%)74.4 V273.23 V (113.85%)93243.0 WDrop/Amp High
4 AWG21.15 mm²85 A104.16 V (43.4%)135.8 V171.82 V (71.59%)58635.1 WDrop/Amp High
3 AWG26.67 mm²100 A82.6 V (34.42%)157.4 V136.26 V (56.77%)46499.1 WDrop/Amp High
2 AWG33.62 mm²115 A65.53 V (27.3%)174.5 V108.09 V (45.04%)36886.7 WDrop/Amp High
1 AWG42.41 mm²130 A51.95 V (21.64%)188.1 V85.69 V (35.7%)29241.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A41.19 V (17.16%)198.8 V67.94 V (28.31%)23184.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A32.67 V (13.61%)207.3 V53.89 V (22.46%)18391.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.92 V (10.8%)214.1 V42.75 V (17.81%)14588.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.55 V (8.56%)219.4 V33.9 V (14.12%)11568.4 WDrop/Amp High
250 kcmil126.7 mm²255 A17.39 V (7.24%)222.6 V28.68 V (11.95%)9787.9 WDrop/Amp High
300 kcmil152.0 mm²285 A14.49 V (6.04%)225.5 V23.91 V (9.96%)8158.8 WDrop/Amp High
350 kcmil177.3 mm²310 A12.43 V (5.18%)227.6 V20.5 V (8.54%)6994.5 WDrop/Amp High
400 kcmil202.7 mm²335 A10.87 V (4.53%)229.1 V17.93 V (7.47%)6118.1 W~ ≤5%
500 kcmil253.4 mm²380 A8.69 V (3.62%)231.3 V14.34 V (5.98%)4894.0 W~ ≤5%
600 kcmil304.0 mm²420 A7.25 V (3.02%)232.8 V11.95 V (4.98%)4079.4 W~ ≤5%
750 kcmil380.0 mm²475 A5.8 V (2.42%)234.2 V9.56 V (3.98%)3263.5 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.35 V (1.81%)235.7 V7.17 V (2.99%)2447.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 600 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 5.8V (2.42%) and delivers 234.2V at the load.

What size aluminum wire is required for 325 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.17V (2.99%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.