🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

325 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 325 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.56V (4.6%)
Voltage at Load End202.2 VLoss: 5.8 V (3263.3 W)
Power & Breaker (125%)117.09 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 325 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1412.21 V (678.95%)0.0 V2329.49 V (1119.95%)794956.5 WDrop/Amp High
12 AWG3.31 mm²20 A887.43 V (426.65%)0.0 V1463.85 V (703.77%)499549.7 WDrop/Amp High
10 AWG5.26 mm²30 A558.44 V (268.48%)0.0 V921.17 V (442.87%)314355.4 WDrop/Amp High
8 AWG8.37 mm²50 A350.94 V (168.72%)0.0 V578.89 V (278.31%)197551.9 WDrop/Amp High
6 AWG13.3 mm²65 A220.86 V (106.18%)0.0 V364.31 V (175.15%)124324.0 WDrop/Amp High
4 AWG21.15 mm²85 A138.88 V (66.77%)69.1 V229.09 V (110.14%)78180.1 WDrop/Amp High
3 AWG26.67 mm²100 A110.14 V (52.95%)97.9 V181.68 V (87.34%)61998.9 WDrop/Amp High
2 AWG33.62 mm²115 A87.37 V (42.01%)120.6 V144.12 V (69.29%)49182.3 WDrop/Amp High
1 AWG42.41 mm²130 A69.26 V (33.3%)138.7 V114.25 V (54.93%)38988.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A54.91 V (26.4%)153.1 V90.58 V (43.55%)30912.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A43.56 V (20.94%)164.4 V71.86 V (34.55%)24521.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A34.55 V (16.61%)173.4 V57.0 V (27.4%)19450.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A27.4 V (13.17%)180.6 V45.2 V (21.73%)15424.5 WDrop/Amp High
250 kcmil126.7 mm²255 A23.18 V (11.15%)184.8 V38.24 V (18.39%)13050.6 WDrop/Amp High
300 kcmil152.0 mm²285 A19.32 V (9.29%)188.7 V31.88 V (15.33%)10878.4 WDrop/Amp High
350 kcmil177.3 mm²310 A16.57 V (7.97%)191.4 V27.33 V (13.14%)9326.1 WDrop/Amp High
400 kcmil202.7 mm²335 A14.49 V (6.97%)193.5 V23.9 V (11.49%)8157.4 WDrop/Amp High
500 kcmil253.4 mm²380 A11.59 V (5.57%)196.4 V19.12 V (9.19%)6525.3 WDrop/Amp High
600 kcmil304.0 mm²420 A9.66 V (4.65%)198.3 V15.94 V (7.66%)5439.2 W~ ≤5%
750 kcmil380.0 mm²475 A7.73 V (3.72%)200.3 V12.75 V (6.13%)4351.3 W~ ≤5%
1000 kcmil506.7 mm²545 A5.8 V (2.79%)202.2 V9.56 V (4.6%)3263.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 325 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 325A load over 800 feet one-way at 208V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.8V (2.79%) and delivers 202.2V at the load.

What size aluminum wire is required for 325 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.56V (4.6%).

What breaker size is needed for a 325A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (325A × 1.25 = 406.2A), which corresponds to a standard 450A circuit breaker.