🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 450 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 6.34V (2.64%)
Voltage at Load End233.9 VLoss: 6.11 V (213.9 W)
Power & Breaker (125%)8.4 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A98.78 V (41.16%)141.2 V162.94 V (67.89%)3457.4 WDrop/Amp High
12 AWG3.31 mm²20 A62.07 V (25.86%)177.9 V102.39 V (42.66%)2172.6 WDrop/Amp High
10 AWG5.26 mm²30 A39.06 V (16.28%)200.9 V64.43 V (26.85%)1367.2 WDrop/Amp High
8 AWG8.37 mm²50 A24.55 V (10.23%)215.5 V40.49 V (16.87%)859.2 WDrop/Amp High
6 AWG13.3 mm²65 A15.45 V (6.44%)224.6 V25.48 V (10.62%)540.7 WDrop/Amp High
4 AWG21.15 mm²85 A9.71 V (4.05%)230.3 V16.02 V (6.68%)340.0 W~ ≤5%
3 AWG26.67 mm²100 A7.7 V (3.21%)232.3 V12.71 V (5.29%)269.6 W~ ≤5%
2 AWG33.62 mm²115 A6.11 V (2.55%)233.9 V10.08 V (4.2%)213.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.84 V (2.02%)235.2 V7.99 V (3.33%)169.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.84 V (1.6%)236.2 V6.34 V (2.64%)134.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.05 V (1.27%)237.0 V5.03 V (2.09%)106.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.42 V (1.01%)237.6 V3.99 V (1.66%)84.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.92 V (0.8%)238.1 V3.16 V (1.32%)67.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.62 V (0.68%)238.4 V2.67 V (1.11%)56.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.35 V (0.56%)238.6 V2.23 V (0.93%)47.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.16 V (0.48%)238.8 V1.91 V (0.8%)40.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.01 V (0.42%)239.0 V1.67 V (0.7%)35.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.81 V (0.34%)239.2 V1.34 V (0.56%)28.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.68 V (0.28%)239.3 V1.11 V (0.46%)23.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.54 V (0.23%)239.5 V0.89 V (0.37%)18.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.41 V (0.17%)239.6 V0.67 V (0.28%)14.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 450 feet one-way at 240V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 6.11V (2.55%) and delivers 233.9V at the load.

What size aluminum wire is required for 35 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 6.34V (2.64%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.