⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

35 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 35 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3/0 AWG85.01 mm² · Drop: 2.69%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 3.57V (2.97%)
Voltage at Load End116.8 VLoss: 3.22 V (112.8 W)
Power & Breaker (125%)4.2 kW45A Breaker Recommended

All AWG & kcmil Wire Gauges for 35 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A131.71 V (109.76%)0.0 V217.26 V (181.05%)4609.8 WDrop/Amp High
12 AWG3.31 mm²20 A82.77 V (68.97%)37.2 V136.52 V (113.77%)2896.8 WDrop/Amp High
10 AWG5.26 mm²30 A52.08 V (43.4%)67.9 V85.91 V (71.59%)1822.9 WDrop/Amp High
8 AWG8.37 mm²50 A32.73 V (27.28%)87.3 V53.99 V (44.99%)1145.6 WDrop/Amp High
6 AWG13.3 mm²65 A20.6 V (17.17%)99.4 V33.98 V (28.31%)720.9 WDrop/Amp High
4 AWG21.15 mm²85 A12.95 V (10.79%)107.0 V21.37 V (17.81%)453.4 WDrop/Amp High
3 AWG26.67 mm²100 A10.27 V (8.56%)109.7 V16.94 V (14.12%)359.5 WDrop/Amp High
2 AWG33.62 mm²115 A8.15 V (6.79%)111.9 V13.44 V (11.2%)285.2 WDrop/Amp High
1 AWG42.41 mm²130 A6.46 V (5.38%)113.5 V10.66 V (8.88%)226.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.12 V (4.27%)114.9 V8.45 V (7.04%)179.3 W~ ≤5%
2/0 AWG67.43 mm²175 A4.06 V (3.39%)115.9 V6.7 V (5.58%)142.2 W~ ≤5%
3/0 AWG85.01 mm²200 A3.22 V (2.69%)116.8 V5.32 V (4.43%)112.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.56 V (2.13%)117.4 V4.22 V (3.51%)89.4 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.16 V (1.8%)117.8 V3.57 V (2.97%)75.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.8 V (1.5%)118.2 V2.97 V (2.48%)63.1 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.55 V (1.29%)118.5 V2.55 V (2.12%)54.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.35 V (1.13%)118.6 V2.23 V (1.86%)47.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.08 V (0.9%)118.9 V1.78 V (1.49%)37.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.9 V (0.75%)119.1 V1.49 V (1.24%)31.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.72 V (0.6%)119.3 V1.19 V (0.99%)25.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.54 V (0.45%)119.5 V0.89 V (0.74%)18.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 35 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 35A load over 600 feet one-way at 120V (1-Phase), you need 3/0 AWG copper wire. This produces a voltage drop of 3.22V (2.69%) and delivers 116.8V at the load.

What size aluminum wire is required for 35 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 3.57V (2.97%).

What breaker size is needed for a 35A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (35A × 1.25 = 43.8A), which corresponds to a standard 45A circuit breaker.