🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

350 Amp Wire Size at 600 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 350 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 1.95%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 10.3V (2.15%)
Voltage at Load End470.6 VLoss: 9.36 V (5675.8 W)
Power & Breaker (125%)290.98 kW450A Breaker Recommended

All AWG & kcmil Wire Gauges for 350 Amps at 600 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1140.63 V (237.63%)0.0 V1881.51 V (391.98%)691471.0 WDrop/Amp High
12 AWG3.31 mm²20 A716.77 V (149.33%)0.0 V1182.34 V (246.32%)434519.6 WDrop/Amp High
10 AWG5.26 mm²30 A451.05 V (93.97%)29.0 V744.02 V (155.0%)273433.4 WDrop/Amp High
8 AWG8.37 mm²50 A283.45 V (59.05%)196.5 V467.57 V (97.41%)171835.1 WDrop/Amp High
6 AWG13.3 mm²65 A178.38 V (37.16%)301.6 V294.25 V (61.3%)108139.8 WDrop/Amp High
4 AWG21.15 mm²85 A112.18 V (23.37%)367.8 V185.04 V (38.55%)68002.8 WDrop/Amp High
3 AWG26.67 mm²100 A88.96 V (18.53%)391.0 V146.74 V (30.57%)53928.0 WDrop/Amp High
2 AWG33.62 mm²115 A70.57 V (14.7%)409.4 V116.41 V (24.25%)42779.9 WDrop/Amp High
1 AWG42.41 mm²130 A55.94 V (11.65%)424.1 V92.28 V (19.22%)33913.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A44.35 V (9.24%)435.6 V73.16 V (15.24%)26888.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A35.18 V (7.33%)444.8 V58.04 V (12.09%)21329.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.91 V (5.81%)452.1 V46.04 V (9.59%)16918.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A22.13 V (4.61%)457.9 V36.51 V (7.61%)13416.6 WDrop/Amp High
250 kcmil126.7 mm²255 A18.73 V (3.9%)461.3 V30.89 V (6.44%)11351.7 WDrop/Amp High
300 kcmil152.0 mm²285 A15.61 V (3.25%)464.4 V25.75 V (5.36%)9462.2 WDrop/Amp High
350 kcmil177.3 mm²310 A13.38 V (2.79%)466.6 V22.07 V (4.6%)8112.0 WDrop/Amp High
400 kcmil202.7 mm²335 A11.7 V (2.44%)468.3 V19.31 V (4.02%)7095.5 WDrop/Amp High
500 kcmil253.4 mm²380 A9.36 V (1.95%)470.6 V15.44 V (3.22%)5675.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A7.8 V (1.63%)472.2 V12.87 V (2.68%)4731.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A6.24 V (1.3%)473.8 V10.3 V (2.15%)3784.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A4.68 V (0.98%)475.3 V7.72 V (1.61%)2838.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 350 amps at 600 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 350A load over 600 feet one-way at 480V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 9.36V (1.95%) and delivers 470.6V at the load.

What size aluminum wire is required for 350 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 10.3V (2.15%).

What breaker size is needed for a 350A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (350A × 1.25 = 437.5A), which corresponds to a standard 450A circuit breaker.