🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

375 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 375 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)500 kcmil253.4 mm² · Drop: 2.21%
Aluminum Wire (≤3% Drop)750 kcmilDrop: 5.06V (2.43%)
Voltage at Load End203.4 VLoss: 4.6 V (2986.3 W)
Power & Breaker (125%)135.1 kW500A Breaker Recommended

All AWG & kcmil Wire Gauges for 375 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A560.13 V (269.29%)0.0 V923.96 V (444.21%)363816.1 WDrop/Amp High
12 AWG3.31 mm²20 A351.99 V (169.22%)0.0 V580.61 V (279.14%)228621.6 WDrop/Amp High
10 AWG5.26 mm²30 A221.5 V (106.49%)0.0 V365.37 V (175.66%)143866.4 WDrop/Amp High
8 AWG8.37 mm²50 A139.2 V (66.92%)68.8 V229.61 V (110.39%)90410.7 WDrop/Amp High
6 AWG13.3 mm²65 A87.6 V (42.12%)120.4 V144.5 V (69.47%)56897.6 WDrop/Amp High
4 AWG21.15 mm²85 A55.09 V (26.48%)152.9 V90.87 V (43.69%)35779.5 WDrop/Amp High
3 AWG26.67 mm²100 A43.68 V (21.0%)164.3 V72.06 V (34.64%)28374.1 WDrop/Amp High
2 AWG33.62 mm²115 A34.65 V (16.66%)173.3 V57.16 V (27.48%)22508.5 WDrop/Amp High
1 AWG42.41 mm²130 A27.47 V (13.21%)180.5 V45.32 V (21.79%)17843.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A21.78 V (10.47%)186.2 V35.93 V (17.27%)14147.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A17.28 V (8.31%)190.7 V28.5 V (13.7%)11222.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A13.71 V (6.59%)194.3 V22.61 V (10.87%)8901.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.87 V (5.23%)197.1 V17.93 V (8.62%)7059.1 WDrop/Amp High
250 kcmil126.7 mm²255 A9.2 V (4.42%)198.8 V15.17 V (7.29%)5972.7 WDrop/Amp High
300 kcmil152.0 mm²285 A7.66 V (3.69%)200.3 V12.64 V (6.08%)4978.5 WDrop/Amp High
350 kcmil177.3 mm²310 A6.57 V (3.16%)201.4 V10.84 V (5.21%)4268.1 WDrop/Amp High
400 kcmil202.7 mm²335 A5.75 V (2.76%)202.3 V9.48 V (4.56%)3733.3 WDrop/Amp High
500 kcmil253.4 mm²380 A4.6 V (2.21%)203.4 V7.58 V (3.65%)2986.3 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A3.83 V (1.84%)204.2 V6.32 V (3.04%)2489.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A3.07 V (1.47%)204.9 V5.06 V (2.43%)1991.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.3 V (1.11%)205.7 V3.79 V (1.82%)1493.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 375 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 375A load over 275 feet one-way at 208V (3-Phase), you need 500 kcmil copper wire. This produces a voltage drop of 4.6V (2.21%) and delivers 203.4V at the load.

What size aluminum wire is required for 375 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 750 kcmil to maintain voltage drop at 5.06V (2.43%).

What breaker size is needed for a 375A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (375A × 1.25 = 468.8A), which corresponds to a standard 500A circuit breaker.