425 Amp Wire Size at 100 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.22%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.8V (1.5%)
Voltage at Load End118.5 VLoss: 1.46 V (620.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 100 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A266.55 V (222.13%)0.0 V439.69 V (366.41%)113285.2 WDrop/Amp High
12 AWG3.31 mm²20 A167.5 V (139.58%)0.0 V276.3 V (230.25%)71188.3 WDrop/Amp High
10 AWG5.26 mm²30 A105.41 V (87.84%)14.6 V173.87 V (144.89%)44797.2 WDrop/Amp High
8 AWG8.37 mm²50 A66.24 V (55.2%)53.8 V109.27 V (91.05%)28152.1 WDrop/Amp High
6 AWG13.3 mm²65 A41.69 V (34.74%)78.3 V68.76 V (57.3%)17716.8 WDrop/Amp High
4 AWG21.15 mm²85 A26.21 V (21.85%)93.8 V43.24 V (36.03%)11141.1 WDrop/Amp High
3 AWG26.67 mm²100 A20.79 V (17.32%)99.2 V34.29 V (28.58%)8835.1 WDrop/Amp High
2 AWG33.62 mm²115 A16.49 V (13.74%)103.5 V27.2 V (22.67%)7008.7 WDrop/Amp High
1 AWG42.41 mm²130 A13.07 V (10.89%)106.9 V21.56 V (17.97%)5556.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.37 V (8.64%)109.6 V17.1 V (14.25%)4405.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.22 V (6.85%)111.8 V13.56 V (11.3%)3494.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.52 V (5.43%)113.5 V10.76 V (8.97%)2771.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.17 V (4.31%)114.8 V8.53 V (7.11%)2198.1 WDrop/Amp High
250 kcmil126.7 mm²255 A4.38 V (3.65%)115.6 V7.22 V (6.02%)1859.8 WDrop/Amp High
300 kcmil152.0 mm²285 A3.65 V (3.04%)116.4 V6.02 V (5.01%)1550.2 WDrop/Amp High
350 kcmil177.3 mm²310 A3.13 V (2.61%)116.9 V5.16 V (4.3%)1329.0 WDrop/Amp High
400 kcmil202.7 mm²335 A2.74 V (2.28%)117.3 V4.51 V (3.76%)1162.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.19 V (1.82%)117.8 V3.61 V (3.01%)929.9 WDrop/Amp High
600 kcmil304.0 mm²420 A1.82 V (1.52%)118.2 V3.01 V (2.51%)775.1 WDrop/Amp High
750 kcmil380.0 mm²475 A1.46 V (1.22%)118.5 V2.41 V (2.01%)620.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.09 V (0.91%)118.9 V1.8 V (1.5%)465.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 100 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 100 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.46V (1.22%) and delivers 118.5V at the load.

What size aluminum wire is required for 425 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.8V (1.5%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.