🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.52%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.26V (1.88%)
Voltage at Load End118.2 VLoss: 1.82 V (775.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A333.19 V (277.66%)0.0 V549.61 V (458.01%)141606.5 WDrop/Amp High
12 AWG3.31 mm²20 A209.38 V (174.48%)0.0 V345.37 V (287.81%)88985.4 WDrop/Amp High
10 AWG5.26 mm²30 A131.76 V (109.8%)0.0 V217.34 V (181.11%)55996.5 WDrop/Amp High
8 AWG8.37 mm²50 A82.8 V (69.0%)37.2 V136.58 V (113.82%)35190.2 WDrop/Amp High
6 AWG13.3 mm²65 A52.11 V (43.42%)67.9 V85.95 V (71.63%)22146.0 WDrop/Amp High
4 AWG21.15 mm²85 A32.77 V (27.31%)87.2 V54.05 V (45.04%)13926.3 WDrop/Amp High
3 AWG26.67 mm²100 A25.99 V (21.65%)94.0 V42.86 V (35.72%)11043.9 WDrop/Amp High
2 AWG33.62 mm²115 A20.61 V (17.18%)99.4 V34.0 V (28.34%)8760.9 WDrop/Amp High
1 AWG42.41 mm²130 A16.34 V (13.62%)103.7 V26.96 V (22.46%)6945.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.96 V (10.8%)107.0 V21.37 V (17.81%)5506.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.28 V (8.56%)109.7 V16.95 V (14.13%)4368.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.15 V (6.79%)111.8 V13.45 V (11.21%)3464.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.46 V (5.39%)113.5 V10.66 V (8.89%)2747.6 WDrop/Amp High
250 kcmil126.7 mm²255 A5.47 V (4.56%)114.5 V9.02 V (7.52%)2324.7 WDrop/Amp High
300 kcmil152.0 mm²285 A4.56 V (3.8%)115.4 V7.52 V (6.27%)1937.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.91 V (3.26%)116.1 V6.45 V (5.37%)1661.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.42 V (2.85%)116.6 V5.64 V (4.7%)1453.1 WDrop/Amp High
500 kcmil253.4 mm²380 A2.73 V (2.28%)117.3 V4.51 V (3.76%)1162.4 WDrop/Amp High
600 kcmil304.0 mm²420 A2.28 V (1.9%)117.7 V3.76 V (3.13%)968.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.82 V (1.52%)118.2 V3.01 V (2.51%)775.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.37 V (1.14%)118.6 V2.26 V (1.88%)581.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 125 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.82V (1.52%) and delivers 118.2V at the load.

What size aluminum wire is required for 425 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.26V (1.88%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.