🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 40 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.49%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.72V (0.6%)
Voltage at Load End119.4 VLoss: 0.58 V (248.0 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 40 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A106.62 V (88.85%)13.4 V175.88 V (146.56%)45314.1 WDrop/Amp High
12 AWG3.31 mm²20 A67.0 V (55.83%)53.0 V110.52 V (92.1%)28475.3 WDrop/Amp High
10 AWG5.26 mm²30 A42.16 V (35.14%)77.8 V69.55 V (57.96%)17918.9 WDrop/Amp High
8 AWG8.37 mm²50 A26.5 V (22.08%)93.5 V43.71 V (36.42%)11260.8 WDrop/Amp High
6 AWG13.3 mm²65 A16.67 V (13.9%)103.3 V27.51 V (22.92%)7086.7 WDrop/Amp High
4 AWG21.15 mm²85 A10.49 V (8.74%)109.5 V17.3 V (14.41%)4456.4 WDrop/Amp High
3 AWG26.67 mm²100 A8.32 V (6.93%)111.7 V13.72 V (11.43%)3534.1 WDrop/Amp High
2 AWG33.62 mm²115 A6.6 V (5.5%)113.4 V10.88 V (9.07%)2803.5 WDrop/Amp High
1 AWG42.41 mm²130 A5.23 V (4.36%)114.8 V8.63 V (7.19%)2222.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.15 V (3.46%)115.9 V6.84 V (5.7%)1762.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.29 V (2.74%)116.7 V5.43 V (4.52%)1397.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.61 V (2.17%)117.4 V4.3 V (3.59%)1108.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.07 V (1.72%)117.9 V3.41 V (2.84%)879.2 WDrop/Amp High
250 kcmil126.7 mm²255 A1.75 V (1.46%)118.2 V2.89 V (2.41%)743.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.46 V (1.22%)118.5 V2.41 V (2.01%)620.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.25 V (1.04%)118.7 V2.06 V (1.72%)531.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.09 V (0.91%)118.9 V1.8 V (1.5%)465.0 WDrop/Amp High
500 kcmil253.4 mm²380 A0.88 V (0.73%)119.1 V1.44 V (1.2%)372.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.73 V (0.61%)119.3 V1.2 V (1.0%)310.0 WDrop/Amp High
750 kcmil380.0 mm²475 A0.58 V (0.49%)119.4 V0.96 V (0.8%)248.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.44 V (0.36%)119.6 V0.72 V (0.6%)186.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 40 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 40 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.58V (0.49%) and delivers 119.4V at the load.

What size aluminum wire is required for 425 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.72V (0.6%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.