🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 75 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.91%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.35V (1.13%)
Voltage at Load End118.9 VLoss: 1.09 V (465.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 75 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A199.92 V (166.6%)0.0 V329.77 V (274.81%)84963.9 WDrop/Amp High
12 AWG3.31 mm²20 A125.63 V (104.69%)0.0 V207.22 V (172.69%)53391.2 WDrop/Amp High
10 AWG5.26 mm²30 A79.05 V (65.88%)40.9 V130.4 V (108.67%)33597.9 WDrop/Amp High
8 AWG8.37 mm²50 A49.68 V (41.4%)70.3 V81.95 V (68.29%)21114.1 WDrop/Amp High
6 AWG13.3 mm²65 A31.26 V (26.05%)88.7 V51.57 V (42.98%)13287.6 WDrop/Amp High
4 AWG21.15 mm²85 A19.66 V (16.38%)100.3 V32.43 V (27.03%)8355.8 WDrop/Amp High
3 AWG26.67 mm²100 A15.59 V (12.99%)104.4 V25.72 V (21.43%)6626.4 WDrop/Amp High
2 AWG33.62 mm²115 A12.37 V (10.31%)107.6 V20.4 V (17.0%)5256.5 WDrop/Amp High
1 AWG42.41 mm²130 A9.8 V (8.17%)110.2 V16.17 V (13.48%)4167.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A7.77 V (6.48%)112.2 V12.82 V (10.69%)3303.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A6.17 V (5.14%)113.8 V10.17 V (8.48%)2620.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.89 V (4.08%)115.1 V8.07 V (6.72%)2078.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.88 V (3.23%)116.1 V6.4 V (5.33%)1648.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.28 V (2.73%)116.7 V5.41 V (4.51%)1394.8 WDrop/Amp High
300 kcmil152.0 mm²285 A2.74 V (2.28%)117.3 V4.51 V (3.76%)1162.7 WDrop/Amp High
350 kcmil177.3 mm²310 A2.35 V (1.95%)117.7 V3.87 V (3.22%)996.8 WDrop/Amp High
400 kcmil202.7 mm²335 A2.05 V (1.71%)117.9 V3.38 V (2.82%)871.9 WDrop/Amp High
500 kcmil253.4 mm²380 A1.64 V (1.37%)118.4 V2.71 V (2.26%)697.4 WDrop/Amp High
600 kcmil304.0 mm²420 A1.37 V (1.14%)118.6 V2.26 V (1.88%)581.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.09 V (0.91%)118.9 V1.81 V (1.5%)465.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.82 V (0.68%)119.2 V1.35 V (1.13%)348.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 75 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 75 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.09V (0.91%) and delivers 118.9V at the load.

What size aluminum wire is required for 425 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.35V (1.13%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.