⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 120 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 1.46%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.17V (1.8%)
Voltage at Load End118.2 VLoss: 1.75 V (744.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 120 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A319.86 V (266.55%)0.0 V527.63 V (439.69%)135942.3 WDrop/Amp High
12 AWG3.31 mm²20 A201.0 V (167.5%)0.0 V331.56 V (276.3%)85426.0 WDrop/Amp High
10 AWG5.26 mm²30 A126.49 V (105.41%)0.0 V208.64 V (173.87%)53756.6 WDrop/Amp High
8 AWG8.37 mm²50 A79.49 V (66.24%)40.5 V131.12 V (109.27%)33782.5 WDrop/Amp High
6 AWG13.3 mm²65 A50.02 V (41.69%)70.0 V82.52 V (68.76%)21260.1 WDrop/Amp High
4 AWG21.15 mm²85 A31.46 V (26.21%)88.5 V51.89 V (43.24%)13369.3 WDrop/Amp High
3 AWG26.67 mm²100 A24.95 V (20.79%)95.1 V41.15 V (34.29%)10602.2 WDrop/Amp High
2 AWG33.62 mm²115 A19.79 V (16.49%)100.2 V32.64 V (27.2%)8410.5 WDrop/Amp High
1 AWG42.41 mm²130 A15.69 V (13.07%)104.3 V25.88 V (21.56%)6667.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.44 V (10.37%)107.6 V20.52 V (17.1%)5286.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.87 V (8.22%)110.1 V16.28 V (13.56%)4193.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.83 V (6.52%)112.2 V12.91 V (10.76%)3326.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.21 V (5.17%)113.8 V10.24 V (8.53%)2637.7 WDrop/Amp High
250 kcmil126.7 mm²255 A5.25 V (4.38%)114.7 V8.66 V (7.22%)2231.7 WDrop/Amp High
300 kcmil152.0 mm²285 A4.38 V (3.65%)115.6 V7.22 V (6.02%)1860.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.75 V (3.13%)116.2 V6.19 V (5.16%)1594.8 WDrop/Amp High
400 kcmil202.7 mm²335 A3.28 V (2.74%)116.7 V5.41 V (4.51%)1395.0 WDrop/Amp High
500 kcmil253.4 mm²380 A2.63 V (2.19%)117.4 V4.33 V (3.61%)1115.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.19 V (1.82%)117.8 V3.61 V (3.01%)930.1 WDrop/Amp High
750 kcmil380.0 mm²475 A1.75 V (1.46%)118.2 V2.89 V (2.41%)744.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.31 V (1.09%)118.7 V2.17 V (1.8%)558.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 120 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 120 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.75V (1.46%) and delivers 118.2V at the load.

What size aluminum wire is required for 425 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.17V (1.8%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.