425 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))
Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 80 ft (24.4 m) one-way run.
Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.44V (1.2%)
Voltage at Load End118.8 VLoss: 1.17 V (496.1 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended
All AWG & kcmil Wire Gauges for 425 Amps at 80 Feet (120V)
| Wire Gauge | Metric Area | NEC 75°C Cu Ampacity | Copper Voltage Drop | Load Voltage | Aluminum Drop | Line Loss ($I^2R$) | NEC Status |
|---|---|---|---|---|---|---|---|
| 14 AWG | 2.08 mm² | 15 A | 213.24 V (177.7%) | 0.0 V | 351.75 V (293.13%) | 90628.2 W | Drop/Amp High |
| 12 AWG | 3.31 mm² | 20 A | 134.0 V (111.67%) | 0.0 V | 221.04 V (184.2%) | 56950.6 W | Drop/Amp High |
| 10 AWG | 5.26 mm² | 30 A | 84.32 V (70.27%) | 35.7 V | 139.1 V (115.91%) | 35837.8 W | Drop/Amp High |
| 8 AWG | 8.37 mm² | 50 A | 52.99 V (44.16%) | 67.0 V | 87.41 V (72.84%) | 22521.7 W | Drop/Amp High |
| 6 AWG | 13.3 mm² | 65 A | 33.35 V (27.79%) | 86.7 V | 55.01 V (45.84%) | 14173.4 W | Drop/Amp High |
| 4 AWG | 21.15 mm² | 85 A | 20.97 V (17.48%) | 99.0 V | 34.59 V (28.83%) | 8912.8 W | Drop/Amp High |
| 3 AWG | 26.67 mm² | 100 A | 16.63 V (13.86%) | 103.4 V | 27.43 V (22.86%) | 7068.1 W | Drop/Amp High |
| 2 AWG | 33.62 mm² | 115 A | 13.19 V (10.99%) | 106.8 V | 21.76 V (18.14%) | 5607.0 W | Drop/Amp High |
| 1 AWG | 42.41 mm² | 130 A | 10.46 V (8.72%) | 109.5 V | 17.25 V (14.38%) | 4444.9 W | Drop/Amp High |
| 1/0 AWG | 53.49 mm² | 150 A | 8.29 V (6.91%) | 111.7 V | 13.68 V (11.4%) | 3524.1 W | Drop/Amp High |
| 2/0 AWG | 67.43 mm² | 175 A | 6.58 V (5.48%) | 113.4 V | 10.85 V (9.04%) | 2795.6 W | Drop/Amp High |
| 3/0 AWG | 85.01 mm² | 200 A | 5.22 V (4.35%) | 114.8 V | 8.61 V (7.17%) | 2217.5 W | Drop/Amp High |
| 4/0 AWG | 107.2 mm² | 230 A | 4.14 V (3.45%) | 115.9 V | 6.83 V (5.69%) | 1758.5 W | Drop/Amp High |
| 250 kcmil | 126.7 mm² | 255 A | 3.5 V (2.92%) | 116.5 V | 5.77 V (4.81%) | 1487.8 W | Drop/Amp High |
| 300 kcmil | 152.0 mm² | 285 A | 2.92 V (2.43%) | 117.1 V | 4.81 V (4.01%) | 1240.2 W | Drop/Amp High |
| 350 kcmil | 177.3 mm² | 310 A | 2.5 V (2.08%) | 117.5 V | 4.13 V (3.44%) | 1063.2 W | Drop/Amp High |
| 400 kcmil | 202.7 mm² | 335 A | 2.19 V (1.82%) | 117.8 V | 3.61 V (3.01%) | 930.0 W | Drop/Amp High |
| 500 kcmil | 253.4 mm² | 380 A | 1.75 V (1.46%) | 118.2 V | 2.89 V (2.41%) | 743.9 W | Drop/Amp High |
| 600 kcmil | 304.0 mm² | 420 A | 1.46 V (1.22%) | 118.5 V | 2.41 V (2.01%) | 620.1 W | Drop/Amp High |
| 750 kcmil | 380.0 mm² | 475 A | 1.17 V (0.97%) | 118.8 V | 1.93 V (1.6%) | 496.1 W | ✓ PASS (≤3%) |
| 1000 kcmil | 506.7 mm² | 545 A | 0.88 V (0.73%) | 119.1 V | 1.44 V (1.2%) | 372.0 W | ✓ PASS (≤3%) |
Frequently Asked Engineering Questions
What size copper wire do I need for 425 amps at 80 feet (120V)?
To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 80 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.17V (0.97%) and delivers 118.8V at the load.
What size aluminum wire is required for 425 amps at 80 feet?
Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.44V (1.2%).
What breaker size is needed for a 425A continuous load?
Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.
Compare Other Distances & Amperages
425 Amp Wire Size by Distance (120V)