⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 50 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.9V (0.75%)
Voltage at Load End119.3 VLoss: 0.73 V (310.0 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 50 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A133.28 V (111.06%)0.0 V219.84 V (183.2%)56642.6 WDrop/Amp High
12 AWG3.31 mm²20 A83.75 V (69.79%)36.2 V138.15 V (115.12%)35594.1 WDrop/Amp High
10 AWG5.26 mm²30 A52.7 V (43.92%)67.3 V86.93 V (72.45%)22398.6 WDrop/Amp High
8 AWG8.37 mm²50 A33.12 V (27.6%)86.9 V54.63 V (45.53%)14076.1 WDrop/Amp High
6 AWG13.3 mm²65 A20.84 V (17.37%)99.2 V34.38 V (28.65%)8858.4 WDrop/Amp High
4 AWG21.15 mm²85 A13.11 V (10.92%)106.9 V21.62 V (18.02%)5570.5 WDrop/Amp High
3 AWG26.67 mm²100 A10.39 V (8.66%)109.6 V17.15 V (14.29%)4417.6 WDrop/Amp High
2 AWG33.62 mm²115 A8.25 V (6.87%)111.8 V13.6 V (11.33%)3504.4 WDrop/Amp High
1 AWG42.41 mm²130 A6.54 V (5.45%)113.5 V10.78 V (8.99%)2778.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.18 V (4.32%)114.8 V8.55 V (7.12%)2202.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.11 V (3.43%)115.9 V6.78 V (5.65%)1747.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.26 V (2.72%)116.7 V5.38 V (4.48%)1385.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.59 V (2.15%)117.4 V4.27 V (3.55%)1099.0 WDrop/Amp High
250 kcmil126.7 mm²255 A2.19 V (1.82%)117.8 V3.61 V (3.01%)929.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.82 V (1.52%)118.2 V3.01 V (2.51%)775.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.56 V (1.3%)118.4 V2.58 V (2.15%)664.5 WDrop/Amp High
400 kcmil202.7 mm²335 A1.37 V (1.14%)118.6 V2.26 V (1.88%)581.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.09 V (0.91%)118.9 V1.8 V (1.5%)464.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.91 V (0.76%)119.1 V1.5 V (1.25%)387.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.73 V (0.61%)119.3 V1.2 V (1.0%)310.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.55 V (0.46%)119.5 V0.9 V (0.75%)232.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 50 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 50 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.73V (0.61%) and delivers 119.3V at the load.

What size aluminum wire is required for 425 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.9V (0.75%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.