🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 175 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.13%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.16V (2.63%)
Voltage at Load End117.4 VLoss: 2.55 V (1085.2 W)
Power & Breaker (125%)51.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 175 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A466.47 V (388.72%)0.0 V769.46 V (641.21%)198249.1 WDrop/Amp High
12 AWG3.31 mm²20 A293.13 V (244.27%)0.0 V483.52 V (402.94%)124579.5 WDrop/Amp High
10 AWG5.26 mm²30 A184.46 V (153.72%)0.0 V304.27 V (253.56%)78395.1 WDrop/Amp High
8 AWG8.37 mm²50 A115.92 V (96.6%)4.1 V191.21 V (159.35%)49266.2 WDrop/Amp High
6 AWG13.3 mm²65 A72.95 V (60.79%)47.0 V120.34 V (100.28%)31004.4 WDrop/Amp High
4 AWG21.15 mm²85 A45.87 V (38.23%)74.1 V75.67 V (63.06%)19496.8 WDrop/Amp High
3 AWG26.67 mm²100 A36.38 V (30.32%)83.6 V60.01 V (50.01%)15461.5 WDrop/Amp High
2 AWG33.62 mm²115 A28.86 V (24.05%)91.1 V47.6 V (39.67%)12265.3 WDrop/Amp High
1 AWG42.41 mm²130 A22.88 V (19.06%)97.1 V37.74 V (31.45%)9723.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A18.14 V (15.12%)101.9 V29.92 V (24.93%)7709.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.39 V (11.99%)105.6 V23.74 V (19.78%)6115.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.41 V (9.51%)108.6 V18.83 V (15.69%)4850.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.05 V (7.54%)110.9 V14.93 V (12.44%)3846.6 WDrop/Amp High
250 kcmil126.7 mm²255 A7.66 V (6.38%)112.3 V12.63 V (10.53%)3254.6 WDrop/Amp High
300 kcmil152.0 mm²285 A6.38 V (5.32%)113.6 V10.53 V (8.77%)2712.9 WDrop/Amp High
350 kcmil177.3 mm²310 A5.47 V (4.56%)114.5 V9.03 V (7.52%)2325.8 WDrop/Amp High
400 kcmil202.7 mm²335 A4.79 V (3.99%)115.2 V7.9 V (6.58%)2034.3 WDrop/Amp High
500 kcmil253.4 mm²380 A3.83 V (3.19%)116.2 V6.32 V (5.26%)1627.3 WDrop/Amp High
600 kcmil304.0 mm²420 A3.19 V (2.66%)116.8 V5.26 V (4.39%)1356.4 WDrop/Amp High
750 kcmil380.0 mm²475 A2.55 V (2.13%)117.4 V4.21 V (3.51%)1085.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.91 V (1.6%)118.1 V3.16 V (2.63%)813.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 175 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 175 feet one-way at 120V (1-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 2.55V (2.13%) and delivers 117.4V at the load.

What size aluminum wire is required for 425 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.16V (2.63%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.